2010-06-29 12:03:22 | 2616 EAST TAMARIND AVENUE | | PERMIT NUMBER 10060529 | | | | 1. WRONG LIFE SAFETY CODE REFERENCED ON PAGE A1.1. | | SHOULD READ NFPA 101-2006 EDITION. | | | | 2. THE SINGLE EXIT SIGN ON PAGE E-1.1 IS DIRECTING | | PERSONS TO WHICH EXIT? PLEASE EXPLAIN RATIONALE. | | | | 3. SINGLE EMERGENCY LIGHT ON PAGE E-1.1 PROVIDES | | ILLUMINATION TO WHICH EXIT ACCESS AREA? PLEASE EXPLAIN | | RATIONALE. | | | | 4. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | WITH NFPA 241. | | | | 5. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR | | WALLS AND CEILINGS. | | | | 6. TACTILE SIGNAGE REQUIRED AT EXIT DOORS. | | | | 7. WINDOW APPEARS BELOW EXIT STAIR. PLEASE REVIEW CODE | | SECTION RELATED TO OPENINGS NEAR AN EXIT STAIR. | | | | 8. PLEASE PROVIDE MORE DETAILS ON THE FIRE | | EXTINGUISHERS THAT ARE SHOWN ON THE PLANS. | | | | 9. NO ELEVATION DRAWINGS PROVIDED WITH PLANS. PLEASE | | SUBMIT ELEVATION DRAWINGS. | | | | 10. BUILDING ADDRESS REQUIRED ON PROPER ELEVATION. A | | MINIMUM OF AT LEAST 6" AND 1" WIDE NUMBERS ARE | | REQUIRED. | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|