2010-07-14 12:09:262007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) BASED ON THE 2009 REVISIONS TO THE 2007 FBC
 REVISIONS, THE STRUCTURE IS LOCATED IN EXPOSURE
 CATEGORY C. PLEASE REVISED PLANS AND ADJUST COMPONENT
 AND CLADDING PRESSURES TO REFLECT EXPOSURE CATEGORY C.
  
 2) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE
 ADDED SPACE AS REQUIRED BY FBC CHAPTER 11. THE FORMS
 ARE REQUIRED TO BE SIGNED AND DATED BY THE PREPARER AND
 THE OWNER/AGENT.
  
 3) SPECIFY THE UNDER FLOOR INSULATION THAT WILL BE
 INSTALLED ON THE PLANS.
  
 4) SHEET AO SPECIFIES SPRAY FOAM INSULATION IN THE
 ROOF. SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS / EVALUATION REPORTS.
  
 5) SPECIFY THE TERMITE TREATMENT THAT WILL BE USED ON
 THE PLANS. SEE FBC R320.
  
 6) FBC R319 REQUIRES WOOD FLOOR JOISTS THAT ARE CLOSER
 THEN 18 INCHES TO EXPOSED GROUND IN CRAWL SPACES TO BE
 PRESERVATIVE TREATED.
  
 7) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  