Plan Review Notes For Permit 10060486 |
Permit Number |
10060486 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-06-22 06:53:32 | INSTALL FIRE ALARM SYSTEM | | PERMIT NUMBER 10060486 | | 2015 BROWARD AVENUE | | | | 1. PLANS INDICATE 2015 SW BROWARD AVENUE. THE CORRECT | | ADDRESS IS 2015 BROWARD AVENUE. | | | | 2. THE NEW FIRE ALARM SYSTEM SHALL BE MONITORED PER | | SECTION 32.3.3.4.6, NEW RESIDENTIAL BOARD AND CARE | | OCCUPANCIES. | | | | 3. EVEN WITH SYSTEM SMOKE DETECTORS, ELECTRIC POWERED | | SMOKE ALARMS ARE REQUIRED IN EACH SLEEPING ROOM, | | OUTSIDE EACH SLEEPING ROOM, AND ALL LEVELS. AN | | ELECTRICAL PERMIT IS REQUIRED PRIOR TO INSTALLATION. | | | | 4. SYSTEM SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM | | OF AT LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS. | | | | 5. THE FIRE ALARM SYSTEM SHALL BE INSTALLED PER THE | | REQUIREMENTS OF NFPA 72, THE NATIONAL FIRE ALARM CODE. | | | | 6. THE REQUIRED FIRE ALARM SYSTEM SHALL BE FULLY | | ADDRESSABLE OR BE WIRED CLASS A, STYLE D. | | | | 7. SYSTEM UPON INSTALLATION IS TO BE COMPLETELY TESTED | | TO ENSURE PROPER OPERATION. | | | | | | APPROVED PROVISO | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|