Plan Review Notes For Permit 10060485 |
Permit Number |
10060485 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-06-22 07:03:31 | INSTALL FIRE ALARM SYSTEM | | PERMIT NUMBER 10060485 | | 2017 BROWARD AVENUE | | | | 1. THE PLANS INDICATE 2017 SW BROWARD AVENUE. THE | | CORRECT STREET ADDRESS IS 2017 BROWARD AVENUE. | | | | 2. THE NEW FIRE ALARM SYSTEM SHALL BE MONITORED PER | | SECTION 32.3.3.4.6, NEW RESIDENTIAL BOARD AND CARE | | OCCUPANCIES. | | | | 3. EVEN WITH SYSTEM SMOKE DETECTORS, ELECTRIC POWERED | | SMOKE ALARMS ARE REQUIRED IN EACH SLEEPING ROOM, | | OUTSIDE EACH SLEEPING AREA, AND ON ALL LEVELS. A PERMIT | | IS REQUIRED PRIOR TO INSTALLATION. | | | | 4. SYSTEM SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM | | OF AT LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS. | | | | 5. THE FIRE ALARM SYSTEM SHALL BE INSTALLED PER THE | | REQUIREMENTS OF NFPA 72, THE NATIONAL FIRE ALARM CODE. | | | | 6. THE REQUIRED FIRE ALARM SYSTEM SHALL BE FULLY | | ADDRESSABLE OR BE WIRED CLASS A, STYLE D. | | | | 7. THE FIRE ALARM SYSTEM WHEN INSTALLED IS TO BE | | COMPLETELY TESTED TO ENSURE PROPER OPERATION. | | | | | | APPROVED PROVISO | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|