2010-06-16 09:47:01RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PERMIT APPLICATION DESCRIBES REPAIR OF 800 S.F. OF
 FLAT ROOF. CLARIFY IF REPAIR OR REPLACEMENT TO VERIFY
 COMPLIANCE WITH SEC. 611 OF 2007 FBC-EXISTING BUILDING.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR FLAT ROOF TO BE INSTALLED.
 CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED. PROVIDE RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY
 GENERAL LIMITATION # 7 ON LAST PAGE OF NOA SUBMITTED.
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 GENERAL LIMITATION #7 REQUIRES IT.
 ***NOTE: TAKE INTO CONSIDERATION THAT THIS BUILDING IS
 LOCATED ON EXPOSURE "C" WHEN DOING THE RAS 117
 CALCULATIONS.
  
 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTES.
  
 4- SEPARATE PERMITS ARE REQUIRED WHEN REMOVING AND
 RELOCATING ANY ROOF EQUIPMENT.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712