Plan Review Notes
Plan Review Notes For Permit 10060347
Permit Number 10060347
Review Stop Z
Sequence Number 1
Notes
Date Text
2010-06-24 15:39:39FAILED
  
 1) PROVIDE A ROOF PLAN OF THE ENTIRE ROOF SHOWING THE
 LOCATION OF THE NEW EQUIPMENT.
  
 2) PROVIDE A SITE PLAN SHOWING THE BUILDING AND THE
 PROPERTY LINES (THIS MAY BE COMBINED WITH THE PLAN
 REQUIRED BY NO. 1).
  
 3) THE HEIGHT DIMENSIONS SHOWN FOR THE "EXHAUST CURB &
 FAN DETAIL" DOES NOT MATCH THE SECTION SHOWN ON SHEET 2
 OF 2. THE DETAIL ON SHEET 1 SHOWS THE EXHAUST CURB AT
 24 INCHES TALL AND THE EXHAUST FAN AS 40 INCHES TALL.
 SHEET 2 PROVIDES A DIMENSION OF 45 INCHES FOR THE CURB
 AND NO DIMENSION FOR THE EXHAUST FAN.
  
 4) PROVIDE THE ACCURATE HEIGHT DIMENSION OF THE EXHAUST
 CURB AND FAN ON SHEET 2 NOT "MINIMUM OF 40 INCHES".
 THEY SCALE AT 7 FEET TALL.
  
 5) PROVIDE THE HEIGHT DIMENSION OF THE "SUPPLY CURB &
 FAN DETAIL" ON SHEET 2.
  
 6) THE DOWNTOWN MASTER PLAN REQUIRES THAT OUTDOOR
 MECHANICAL EQUIPMENT BE SCREENED. PROVIDE DETAILS ON
 HOW THE PROPOSED FAN EQUIPMENT WILL BE SCREENED.
  
 7) PROVIDE ELEVATIONS WHICH ACCURATELY DEPICT THE
 BUILDING INCLUDING THE PROPOSED FAN EQUIPMENT AND THE
 SCREENING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.