Plan Review Notes For Permit 10060347 |
Permit Number |
10060347 |
|
Review Stop |
Z |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-06-24 15:39:39 | FAILED | | | | 1) PROVIDE A ROOF PLAN OF THE ENTIRE ROOF SHOWING THE | | LOCATION OF THE NEW EQUIPMENT. | | | | 2) PROVIDE A SITE PLAN SHOWING THE BUILDING AND THE | | PROPERTY LINES (THIS MAY BE COMBINED WITH THE PLAN | | REQUIRED BY NO. 1). | | | | 3) THE HEIGHT DIMENSIONS SHOWN FOR THE "EXHAUST CURB & | | FAN DETAIL" DOES NOT MATCH THE SECTION SHOWN ON SHEET 2 | | OF 2. THE DETAIL ON SHEET 1 SHOWS THE EXHAUST CURB AT | | 24 INCHES TALL AND THE EXHAUST FAN AS 40 INCHES TALL. | | SHEET 2 PROVIDES A DIMENSION OF 45 INCHES FOR THE CURB | | AND NO DIMENSION FOR THE EXHAUST FAN. | | | | 4) PROVIDE THE ACCURATE HEIGHT DIMENSION OF THE EXHAUST | | CURB AND FAN ON SHEET 2 NOT "MINIMUM OF 40 INCHES". | | THEY SCALE AT 7 FEET TALL. | | | | 5) PROVIDE THE HEIGHT DIMENSION OF THE "SUPPLY CURB & | | FAN DETAIL" ON SHEET 2. | | | | 6) THE DOWNTOWN MASTER PLAN REQUIRES THAT OUTDOOR | | MECHANICAL EQUIPMENT BE SCREENED. PROVIDE DETAILS ON | | HOW THE PROPOSED FAN EQUIPMENT WILL BE SCREENED. | | | | 7) PROVIDE ELEVATIONS WHICH ACCURATELY DEPICT THE | | BUILDING INCLUDING THE PROPOSED FAN EQUIPMENT AND THE | | SCREENING. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|