2010-06-18 15:09:56*****DENIED*****
  
 1) THE ENTRANCE AREA OF 204 SQ.FT. DIVIDED BY 5 SQ.FT.
 PER PERSON EQUALS 41 PERSONS. THE OCCUPANT LOAD IS ONLY
 SHOWN AS 22 PERSONS.
  
 2) THE OCCUPANT LOAD ON THE PLANS SHOULD EITHER BE THE
 NUMBER OF FIXED SEATS OR THE FLOOR AREA DIVIDED BY THE
 OCCUPANT LOAD FACTOR, NOT BOTH. EXAMPLE: DINING AREA 3
 SHOWS "60 SEATS (LOAD 68 PERSONS)." ALSO THE LIFE
 SAFETY DATA CHART SHOWS 617 SQ.FT. FOR DINING AREA 3
 WITH 7SQ.FT. PER PERSON. 617SQ.FT. DIVIDED BY 7 SQ.FT.
 EQUALS 88 PERSONS NOT 28 PERSONS.
  
 3) THE FIXED BOOTH OCCUPANT CALCULATION SHOULD BE BASED
 UPON 18" PER PERSON NOT 24" PER PERSON. REFERENCE
 FLORIDA FIRE PREVENTION CODE (NFPA 101) TABLE 7.3.1.2.
  
 4) THE OCCUPANT LOAD FOR DINING AREA 2 DOES NOT INCLUDE
 THE FIVE WHEELCHAIR SPACES.
  
 5) WHY DOES THE FLOOR AREA PER OCCUPANT VARY BETWEEN
 THE DINING AREAS FROM 15 SQ.FT. PER PERSON TO 7 SQ.FT.
 PER PERSON?
  
  
 CAPT. MICHAEL A. WILLIAMS
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6722
 561-805-6730