Plan Review Notes For Permit 10060335 |
Permit Number |
10060335 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-06-18 15:09:56 | *****DENIED***** | | | | 1) THE ENTRANCE AREA OF 204 SQ.FT. DIVIDED BY 5 SQ.FT. | | PER PERSON EQUALS 41 PERSONS. THE OCCUPANT LOAD IS ONLY | | SHOWN AS 22 PERSONS. | | | | 2) THE OCCUPANT LOAD ON THE PLANS SHOULD EITHER BE THE | | NUMBER OF FIXED SEATS OR THE FLOOR AREA DIVIDED BY THE | | OCCUPANT LOAD FACTOR, NOT BOTH. EXAMPLE: DINING AREA 3 | | SHOWS "60 SEATS (LOAD 68 PERSONS)." ALSO THE LIFE | | SAFETY DATA CHART SHOWS 617 SQ.FT. FOR DINING AREA 3 | | WITH 7SQ.FT. PER PERSON. 617SQ.FT. DIVIDED BY 7 SQ.FT. | | EQUALS 88 PERSONS NOT 28 PERSONS. | | | | 3) THE FIXED BOOTH OCCUPANT CALCULATION SHOULD BE BASED | | UPON 18" PER PERSON NOT 24" PER PERSON. REFERENCE | | FLORIDA FIRE PREVENTION CODE (NFPA 101) TABLE 7.3.1.2. | | | | 4) THE OCCUPANT LOAD FOR DINING AREA 2 DOES NOT INCLUDE | | THE FIVE WHEELCHAIR SPACES. | | | | 5) WHY DOES THE FLOOR AREA PER OCCUPANT VARY BETWEEN | | THE DINING AREAS FROM 15 SQ.FT. PER PERSON TO 7 SQ.FT. | | PER PERSON? | | | | | | CAPT. MICHAEL A. WILLIAMS | | & WESLEY JOLIN | | FIRE PLAN REVIEW | | 561-805-6722 | | 561-805-6730 |
|