Plan Review Notes For Permit 10060335 |
Permit Number |
10060335 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-06-23 18:02:45 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. IT IS NOT CLEAR HOW YOU HAVE OBTAINED FLOOR AREA. | | | | FOR INSTANCE: | | VESTIBULE/WAITING AREA APPEARS TO BE APPROXIMATELY 300 | | SQUARE FEET, BUT LIFE SAFETY DATA ON SHEET A101 SHOWS | | 204 SF. | | DINING AREA 1 IS APPROX. 8X26, 208SF, BUT LIFE SAFETY | | DATA FLOOR AREA IS 155 FOR THE TABLE/CHAIRS AREA. | | | | THIS COMMENT APPLIES TO OTHER AREAS. PLEASE EITHER | | REVISE THE LIFE SAFETY DATA, FLOOR AREA OR SHOW HOW THE | | FLOOR AREA HAS BEEN DETERMINED (PROVIDE CLEAR | | DIMENSIONS ON THE PLAN FOR EACH AREA). | | | | 2. PLEASE EXPLAIN THE DIFFERENCE BETWEEN "MAXIMUM | | OCCUPANCY" AND "OCCUPANCY LOAD." SEE FBC1004.1.1, THE | | OCCUPANT LOAD CANNOT BE LESS THAN THE TABLE, BUT IF | | DESIGN OCCUPANT LOAD IS HIGHER, THAT NUMBER SHOULD BE | | USED. FOR INSTANCE, ENTRANCE, 204SF, 5SF PER PERSON, | | SHOULD HAVE AN OCCUPANT LOAD OF 41. LIFE SAETY DATA | | SHOWS 36 AND 22. SEE ALSO COMMENT #1 REGARDING FLOOR | | AREA. IF THE VESTIBULE/WAITING AREA IS 300SF, OCCUPANT | | LOAD SHOULD BE 60 BASED ON SQUARE FOOT AREA. | | | | PLEASE FEEL FREE TO CONTACT ME TO DISCUSS OR TO EMAIL | | EXPLANATORY INFORMATION. | | |
|