Plan Review Notes
Plan Review Notes For Permit 10060335
Permit Number 10060335
Review Stop B
Sequence Number 1
Notes
Date Text
2010-06-23 18:02:45****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. IT IS NOT CLEAR HOW YOU HAVE OBTAINED FLOOR AREA.
  
 FOR INSTANCE:
 VESTIBULE/WAITING AREA APPEARS TO BE APPROXIMATELY 300
 SQUARE FEET, BUT LIFE SAFETY DATA ON SHEET A101 SHOWS
 204 SF.
 DINING AREA 1 IS APPROX. 8X26, 208SF, BUT LIFE SAFETY
 DATA FLOOR AREA IS 155 FOR THE TABLE/CHAIRS AREA.
  
 THIS COMMENT APPLIES TO OTHER AREAS. PLEASE EITHER
 REVISE THE LIFE SAFETY DATA, FLOOR AREA OR SHOW HOW THE
 FLOOR AREA HAS BEEN DETERMINED (PROVIDE CLEAR
 DIMENSIONS ON THE PLAN FOR EACH AREA).
  
 2. PLEASE EXPLAIN THE DIFFERENCE BETWEEN "MAXIMUM
 OCCUPANCY" AND "OCCUPANCY LOAD." SEE FBC1004.1.1, THE
 OCCUPANT LOAD CANNOT BE LESS THAN THE TABLE, BUT IF
 DESIGN OCCUPANT LOAD IS HIGHER, THAT NUMBER SHOULD BE
 USED. FOR INSTANCE, ENTRANCE, 204SF, 5SF PER PERSON,
 SHOULD HAVE AN OCCUPANT LOAD OF 41. LIFE SAETY DATA
 SHOWS 36 AND 22. SEE ALSO COMMENT #1 REGARDING FLOOR
 AREA. IF THE VESTIBULE/WAITING AREA IS 300SF, OCCUPANT
 LOAD SHOULD BE 60 BASED ON SQUARE FOOT AREA.
  
 PLEASE FEEL FREE TO CONTACT ME TO DISCUSS OR TO EMAIL
 EXPLANATORY INFORMATION.
  