2010-07-08 09:25:24BUILDING PROVISO:
 424.2.17.1.8 ACCESS GATES, WHEN PROVIDED, SHALL BE
 SELF-CLOSING AND SHALL COMPLY WITH THE REQUIREMENTS OF
 SECTIONS 424.2.17.1.1 THROUGH 424.2.17.1.7 AND SHALL BE
 EQUIPPED WITH A SELF-LATCHING LOCKING DEVICE LOCATED ON
 THE POOL SIDE OF THE GATE. WHERE THE DEVICE RELEASE IS
 LOCATED NO LESS THAN 54 INCHES (1372 MM) FROM THE
 BOTTOM OF THE GATE, THE DEVICE RELEASE MECHANISM MAY BE
 LOCATED ON EITHER SIDE OF THE GATE AND SO PLACED THAT
 IT CANNOT BE REACHED BY A YOUNG CHILD OVER THE TOP OR
 THROUGH ANY OPENING OR GAP FROM THE OUTSIDE. GATES THAT
 PROVIDE ACCESS TO THE SWIMMING POOL MUST OPEN OUTWARD
 AWAY FROM THE POOL. THE GATES AND BARRIER SHALL HAVE NO
 OPENING GREATER THAN 1/2 INCH (12.7 MM) WITHIN 18
 INCHES (457 MM) OF THE RELEASE MECHANISM.
  