Plan Review Notes
Plan Review Notes For Permit 10060288
Permit Number 10060288
Review Stop B
Sequence Number 1
Notes
Date Text
2010-06-21 18:21:03****CORRECTIONS****
 ****DCA MODEL FMT2356A***MFGR MODEL FERN (BAYBERRY)***
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FBC R408.2, SPECIFY VENTILATION OPENING SIZE TO SHOW
 COMPLIANCE WITH THE FBC REQUIREMENT.
  
 2. ACCESS IS SHOWN UNDER THE PORCH. ENGINEER'S NOTE
 STATES THAT ACCESS IS NOT TO BE LOCATED UNDER THE
 PORCH. THIS LOCATION PROHIBITS ACCESS TO THE OTHER
 SECTION OF CRAWL SPACE. PROVIDE ACCESS TO ALL AREAS OF
 THE CRAWL SPACE FBC408.2.
  
 3. SK3 EXTERIOR STEM WALL SHOWS 8" MIN FROM GRADE TO
 BOTTOM OF FLOOR. SEE FBC R408.4, IF EXTERIOR GRADE IS
 AT 8", AN ACCESS AREA COMPLYING WITH FBC R408.4 SHALL
 BE PROVIDED. IN ORDER TO AVOID FIELD ISSUES, IT IS
 SUGGESTED THAT A DETAIL OR SPECIFICATION WITH SPECIFIC
 REQUIREMENTS BE PROVIDED.
  
  
  
 THE FOLLOWING DOES NOT NEED TO BE ADDRESSED, AVISORY
 ONLY:
  
 AFTER ISSUANCE OF THE MASTER, SITE PERMITS WILL
 REQUIRE:
  
 1. SOILS INVESTIGATION REPORT, 2000 PSF BEARING MINIMUM
 2. CURRENT SURVEY
 3. SITE PLAN SHOWING PROPOSED LOCATION (ZONING REVIEW
 REQUIRED)
 4. PROPOSED FINISHED FLOOR ELEVATION FBC403.1.7.3.
 5. STAIR OR DOOR LANDING DETAIL
 6. DETAIL FOR STRUCTURAL CONNECTION BETWEEN MODULES
 7 SEPARATE PERMITS FOR ELECTRIC HOOKUP, PLUMBING
 HOOKUP, MECHANICAL, IMPACT PROTECTION, ROOF
 8. SITE SPECIFIC ENERGY CALCS REQUIRED
 9. IMPACT FEE ASSESSMENT - PLANS ARE TO BE STAMPED AND
 THE RECEIPT ATTACHED TO APPLICATION
  
  
  
  
  