Plan Review Notes For Permit 10060287 |
Permit Number |
10060287 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-07-27 09:39:15 | ****CORRECTIONS**** | | ****DCA MODEL FMP4586C***MFGR MODEL ALTHEA*** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. AS DISCUSSED, PLEASE INCLUDE THE STAIR DETAIL WITH | | THE MASTER PERMITS. PLEASE REVISE THE DETAIL TO | | INCLUDE: | | | | FBC311.5.3.2, THE SUM OF TWO RISERS AND A TREAD TO | | EQUAL NOT LESS THAN 24" NOR MORE THAN 25". | | | | SPECIFY STRINGER ATTACHMENT, TOP AND BOTTOM. | | | | SPECIFY GUARD OPENING LIMITATIONS FBC R312.2 AND STAIR | | RAIL HEIGHT FBC R 311.5.6.1. | | | | 2. AS DISCUSSED, THE MATING DETAIL WILL BE INCLUDED IN | | THE MASTER PERMITS. PLEASE PROVIDE AN ORIGINAL UNIT | | CONNECTION DETAIL, AND REVISE THE SECOND SHEET TO | | INCLUDE THE TITLE BLOCK OF THE PERSON RESPONSIBLE FOR | | THE DESIGN AND HAVE THE DOCUMENT SIGNED AND SEALED. | | FS471. | | | | 3. ONLY ONE SET OF DCA PLANS WAS SUBMITTED, TWO SETS OF | | STRUCTURALS. PLEASE PROVIDE TWO IDENTICAL COLLATED SETS | | OF PLANS FOR PERMIT ISSUANCE. | | | | | | |
|