Plan Review Notes
Plan Review Notes For Permit 10060240
Permit Number 10060240
Review Stop E
Sequence Number 1
Notes
Date Text
2010-06-22 13:33:13 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE SECTION 13-415.2.ABC.1. AND 13-415.2.C
 REFERENCED ON SHEET E-9 ARE FROM THE 2004 BUILDING CODE
 SEE ABOVE REFERENCED CODES FOR THE CURRENTLY ADOPTED
 CODES.
  
 2} 4.1 WATTS PER SQ/FT SHOWN IN THE "LUMINARY
 SCHEDULE", SHEET E-9 IS MUCH HIGHER THAN THE ALLOWED
 WATTAGES IN TABLE 13-415.B.1, 2007 FBC.
  
 3} THE 2005 NEC IS REFERENCED ON SHEET E-9 ALSO 220.20,
 220.11, 220.13, 220.15ON THE PANEL SCHEDULES ARE NOT
 ARTICLES IN THE 2008 NEC.
  
 4}PANEL 7LC CURCUITS #2, 4, 15 AND 22 HAVE # 12
 CONDUCTORS ON A 25 AMP OVERCURRENT DEVICE IN VIOLATION
 OF TABLE 310.16 AND 240.2(D) NEC.
  
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  