Plan Review Notes For Permit 10060240 |
Permit Number |
10060240 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-06-22 13:33:13 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008 | | NEC, 2004 FBC AS AMENDED, CHAPTER 1AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE SECTION 13-415.2.ABC.1. AND 13-415.2.C | | REFERENCED ON SHEET E-9 ARE FROM THE 2004 BUILDING CODE | | SEE ABOVE REFERENCED CODES FOR THE CURRENTLY ADOPTED | | CODES. | | | | 2} 4.1 WATTS PER SQ/FT SHOWN IN THE "LUMINARY | | SCHEDULE", SHEET E-9 IS MUCH HIGHER THAN THE ALLOWED | | WATTAGES IN TABLE 13-415.B.1, 2007 FBC. | | | | 3} THE 2005 NEC IS REFERENCED ON SHEET E-9 ALSO 220.20, | | 220.11, 220.13, 220.15ON THE PANEL SCHEDULES ARE NOT | | ARTICLES IN THE 2008 NEC. | | | | 4}PANEL 7LC CURCUITS #2, 4, 15 AND 22 HAVE # 12 | | CONDUCTORS ON A 25 AMP OVERCURRENT DEVICE IN VIOLATION | | OF TABLE 310.16 AND 240.2(D) NEC. | | | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|