2010-06-10 10:05:35PLUMBING REVIEW #1
 DENIED
  
 SHEET 3.0P & 3.1P - THE ADA W.C. IN THE WOMENS RESTROOM
 HAS NO VENT.
  
 SHEET 3.0P & 3.1P - A DRY VENT IS REQUIRED BETWEEN THE
 OTHER 2 WATER CLOSETS (A URINAL IS NOT INCLUDED IN THE
 DEFINITION OF A BATHROOM GROUP). THE ADA W.C. IN THE
 WOMENS RESTROOM COULD BE CONNECTED TO THIS CURCIT VENT
 GROUP.
  