Plan Review Notes For Permit 10060156 |
Permit Number |
10060156 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-06-10 10:05:35 | PLUMBING REVIEW #1 | | DENIED | | | | SHEET 3.0P & 3.1P - THE ADA W.C. IN THE WOMENS RESTROOM | | HAS NO VENT. | | | | SHEET 3.0P & 3.1P - A DRY VENT IS REQUIRED BETWEEN THE | | OTHER 2 WATER CLOSETS (A URINAL IS NOT INCLUDED IN THE | | DEFINITION OF A BATHROOM GROUP). THE ADA W.C. IN THE | | WOMENS RESTROOM COULD BE CONNECTED TO THIS CURCIT VENT | | GROUP. | | | | REVIEW BY LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | (561) 805-6692 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | |
|