Plan Review Notes For Permit 10060156
Permit Number 10060156
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-06-11 13:06:54*****DENIED*****
  
  
 1. PLEASE INDICATE IF THIS IS AN EXISTING OR NEW
 ASSEMBLY OCCUPANCY.
  
 2. ON SHEET C-1, EDIT TO REFLECT THE FOLLOWING: 2006
 NFPA 101, 2007 FLORIDA FIRE PREVENTION CODE, NFPA 241 -
 2004 EDITION.
  
 3. PLAN INDICATES THAT THE PROJECT LOCATION IS FIRE
 SPRINKLERED. PROVIDE A FIRE SPRINKLER HEAD LAYOUT FOR
 THE PROPOSED SPACE.
  
 4. PLEASE INDICATE HOW THE FIRE SPRINKLER SYSTEM IS
 MONITORED.
  
 5. PANIC HARDWARE OF FIRE EXIT HARDWARE SHALL BE
 REQUIRED ON ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS.
  
 6. COMMERCIAL COOKING EQUIPMENT SHALL BE PROTECTED IN
 ACCORDANCE WITH NFPA 96 - 2004 EDITION.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW