Date |
Text |
2010-06-09 14:42:09 | PLUMBING REVIEW |
| DENIED: |
| |
| SHEETS A-1 & A-2: |
| WATER CLOSETS IN STALLS IN ACCESSIBLE STALLS SHALL |
| COMPLY WITH FIGURE 30E |
| FBC 2007 11-4.1.3(11) TOILET FACILITIES. IF TOILET |
| ROOMS ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE |
| TOILET ROOM SHALL COMPLY WITH SECTION 11-4.22. |
| WATER CLOSETS IN ACCESSIBLE STALLS SHALL COMPLY WITH |
| FIGURE 30E |
| |
| SHEET P-1 |
| 1. FBC 2004 WPB AMENDMENTS106.3.5.1.3 : DOMESTIC WATER |
| RISER DIAGRAM REQUIRED. |
| |
| 2. A VENT IS REQUIRED BETWEEN THE 2 SHOWERS- FBC 2007 |
| PLUMBING 901.2.1 VENTING REQUIRED. EVERY TRAP AND |
| TRAPPED FIXTURE SHALL BE VENTED IN ACCORDANCE WITH ONE |
| OF THE VENTING METHODS SPECIFIED IN THIS CHAPTER. |
| |
| 3. THE VERTICAL DRY VENT BETWEEN THE SHOWERS MAY SERVE |
| AS THE CURCUIT VENT FOR THE 4 WATER CLOSETS ON THE |
| SECOND FLOOR |
| 911.2 VENT CONNECTION. THE CIRCUIT VENT CONNECTION |
| SHALL BE LOCATED BETWEEN THE TWO MOST UPSTREAM FIXTURE |
| DRAINS. THE VENT SHALL CONNECT TO THE HORIZONTAL BRANCH |
| AND SHALL BE INSTALLED IN ACCORDANCE WITH SECTION 905. |
| THE CIRCUIT VENT PIPE SHALL NOT RECEIVE THE DISCHARGE |
| OF ANY SOIL OR WASTE. |
| |
| 4. A URINAL ON THE 2ND FLOOR IS LABELED AS SINK. |
| |
| 5. THE SOIL STACK SERVING THE 2ND FLOOR REQUIRES A |
| CLEANOUT. |
| |
| 6. 911.3 THE WASTE FROM THE 2ND FLOOR IS NOT PERMITTED |
| TO FLOW THROUGH THE 1ST FLOOR CURCUIT VENT. ATTACH THE |
| 2ND FLOOR DOWNSTREAM OF THE 1ST WATER CLOSET ON THE 1ST |
| FLOOR. |
| |
| 7. A DRY VERTICAL CURCUIT VENT IS REQUIERED BETWEEN THE |
| TWO MOST UPSTREAM WATER CLOSETS ON THE FIRST FLOOR. |
| |
| 8. 20 FIXTURE UNITS ARE MAXIMUM FOR A 3" BRANCH. 4" |
| PIPE IS REQUIRED UP TO THE BRANCHES BEFORE THE WATER |
| CLOSETS ON THE SECOND FLOOR. |
| |