2010-06-16 13:56:51PLANS DENIED
 1) PLEASE IDENTIFY WALLS WITH A KEY ON THE LIFE SAFTY
 PLANS .
 2) PLEASE PROVIDE A LIFE SAFTY PLAN WITH THE PLANS.
 3) PLEASE REFER TO SECTION 607.5.1 FIRE WALLS.
 4) PLEASE REFER TO SECTION607.7 FLEXIBLE DUCT AND AIR
 CONNECTORS .
 5) PLEASE REFER TO SECTION 607.8 LOCATION AND
 INSTALLATION DETAILS .
 6) PLEASE REFER TO TABLE 403.3 OUT DOOR VENTILATION
 PUBLIC SPACES ( TOILET ROOMS )
 7) PLEASE SHOW ON THE PLANS WHERE THE FRESH AIR
 CALCULATIONS ARE COMING FROM .
 8) PLEASE IDENTIFY THE EQUIPMENT ON THE PLANS (AHU #1
 AND THE SIZE OF EQUIPMENT)
 9) PLANS MUST BE CEILED BY ARCHITECT OR ENGINEER .
 10) PLEASE REFER TO SECTION 601.4 BALANCED RETURN AIR .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732