2010-06-09 12:37:59THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
  
 1} THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE
 13-415.1AB.1.1 FOR TIME CLOCK REQUIREMENTS. ALL THAT IS
 REQUIRED FOR THE ELECTRICAL REVIEW IS THE BASIC
 PRESCRIPTIVE REQUIREMENTS. SEE 13-415.2.AB.5 INTERIOR
 LIGHTING POWER, SCOPE.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED
 INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH
 SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR
 LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE
 DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF
 THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE
 DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE
 SCHEDULE TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.
  
 2} SUBMIT A LEGEND OF FIXTURE TYPES AND WATTAGES ON THE
 PLAN TO CORRELATE WITH THE ONES IN THE CALCULATIONS.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  