2010-06-09 12:37:59 | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005 |
| NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED, |
| CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| |
| |
| 1} THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE |
| 13-415.1AB.1.1 FOR TIME CLOCK REQUIREMENTS. ALL THAT IS |
| REQUIRED FOR THE ELECTRICAL REVIEW IS THE BASIC |
| PRESCRIPTIVE REQUIREMENTS. SEE 13-415.2.AB.5 INTERIOR |
| LIGHTING POWER, SCOPE. |
| THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR |
| A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING |
| SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD |
| DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE |
| METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED |
| INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH |
| SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR |
| LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH |
| SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE |
| DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF |
| THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE |
| DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE |
| SCHEDULE TO CORRELATE WITH THE ONES IN THE |
| CALCULATIONS. |
| |
| 2} SUBMIT A LEGEND OF FIXTURE TYPES AND WATTAGES ON THE |
| PLAN TO CORRELATE WITH THE ONES IN THE CALCULATIONS. |
| |