2010-06-08 12:29:02BUILDING PLAN REVIEW
 PERMIT:10050105/
 REVISION: 10060054
 ADD: 500 FERN ST
 CONT: MINUTEMAN CONSTRUCTION
 TEL: (561)644-9426
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 NOTE BUILDING TYPE: II-B, UNPROTECTED / SPRINKLED
  
 1) COVERSHEET INDICATES THE LEVEL OF ALTERATION TO BE
 LEVEL 1. PLEASE REVIEW 2007 FBC EXIST BLDG CODE SECTION
 404.1.
 404.1 SCOPE. LEVEL 2 ALTERATIONS INCLUDE THE
 RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION
 OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION
 OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL
 EQUIPMENT.
  
 2) SHEET A-1:
 2A) IN THE UPPER RIGHT CORNER OF THE PLANS, THEY SHOW
 AN EXISTING VERTICAL EXIT ENCLOSURE WITH TWO ISSUES:
  
 2A)(1) THE VERTICAL EXIT ENCLOSURE DOES NOT HAVE ??
 HOUR FIRE RATED DOORS SEPARATING IT FROM THE REMAINDER
 OF THE EXIT ACCESS CORRIDORS. SINCE THERE IS NO
 SEPARATION THE HORIZONTAL EXTENSION OF THE VERTICAL
 EXIT ( 1 HR/ FBC- 1020.1) WOULD BE CONSIDERED A EXIT
 PASSAGEWAY REQUIRING THE CONTINUATION OF ONE HOUR RATED
 WALLS WITH ONE HOUR OPENING PROTECTIVE???S ( FBC-TABLE
 715.4 SHAFTS/ EXIT ENCLOSURES & EXIT PASSAGE WAYS).
  
 2A)(2) THE PLANS SHOW AN EXISTING ELEVATOR SHAFT WITH
 DOORS OPENING INTO THE VERTICAL EXIT. PERMIT #
 91-B-02716 ON THE FIRST FLOOR INDICATED THE SHAFT TO BE
 WALLED UP AND THE PLANS ALSO INDICATE SHOP DRAWINGS
 WITH A NEW INFILL OF THE SECOND FLOOR WITHIN THE
 ELEVATOR SHAFT WITH STEEL SHOP DRAWINGS, ELIMINATING
 THE USE OF THE ELEVATOR.
 2007 FBC 1020.1 ELEVATOR SHAFTS SHALL NOT OPEN INTO AN
 EXIT ENCLOSURE.
  
 2B) THE CORRIDORS WITH WALL TAG #4 INDICATE A 1 HR
 RATING BUT THE PLANS DO NOT INDICATE THE CONSTRUCTION
 OF THE OTHER NEW WALL TYPES. NO OTHER WALL TAGS ARE
 INDICATED. PLANS WILL NEED TO IDENTIFY WALL
 CONSTRUCTION BY STUD TYPE MATERIAL, SIZE, SPACING AND
 WALL FINISH MATERIALS. FBC-B 106.1.2 ADDITIONAL
 INFORMATION REQUIRED,
 FBC-B 603.1 & FBC-B TABLE 1017.1.
 2C) DOOR IDENTIFICATION INDICATES F.R. I TAKE THIS TO
 BE FIRE RATED DOORS BUT THERE IS NO LEGEND TO PROVIDE
 THE HOURLY RATING REQUIRED 2007 FBC-B TABLE 715.4 AND
 IF THERE IS TO BE ANY GLAZED OPENINGS WITHIN THE FIRE
 RATED DOORS (TABLE 715.5 & TABLE 715.5.3.
  
 2D) THE BOX OFFICE INDICATES THE USE OF A SLIDING GLASS
 WINDOW WHICH AS SHOWN IS STILL LOCATED WITHIN A EXIT
 PASSAGE WAY REQUIRING A ONE HOUR WALL RATING AS WELL AS
 A ONE HOUR OPENING PROTECTIVE PER TABLE 715.4. THE
 OTHER ISSUE WITH THIS AREA THE WALL RATING IS
 ELIMINATED, PLEASE REVIEW 2007 FBC-B TABLE 1017.1 FOR
 ASSEMBLY OCCUPANCIES.
  
 2E) THE PERFORMANCE SPACE WILL NEED TO INDICATE WHERE
 THE PUBLIC SEATING IS LOCATED AS WELL AS THE STAGE
 LOCATION, PLEASE PROVIDE A LIFE SAFETY PLAN FOR BOTH
 THE FIRST AND SECOND FLOORS. 2007 FBC-B 106.3.5.1.1
 MINIMUM PLAN REVIEW REQUIREMENTS.
  
 2F) COSTUME SHOP- IS THIS A MERCANTILE OR RETAIL AREA?
  
 2G) SCENE SHOP PLEASE PROVIDE ADDITIONAL INFORMATION.
 WHAT IS THE PURPOSE OR USE OF THIS SPACE, WILL SCENES
 AND PROPS BE STORED THERE OR WILL THEY BE BUILT THERE.
 IF THE SCENES ARE BEING BUILT THERE WILL THERE BE
 CONSTRUCTION DUST AS SAW DUST?
 COMBUSTIBLE DUST. FINELY DIVIDED SOLID MATERIAL THAT IS
 420 MICRONS OR LESS IN DIAMETER AND WHICH, WHEN
 DISPERSED IN AIR IN THE PROPER PROPORTIONS, COULD BE
 IGNITED BY A FLAME, SPARK OR OTHER SOURCE OF IGNITION.
 COMBUSTIBLE DUST WILL PASS THROUGH A U.S. NO. 40
 STANDARD SIEVE.
 DEFLAGRATION. AN EXOTHERMIC REACTION, SUCH AS THE
 EXTREMELY RAPID OXIDATION OF A FLAMMABLE DUST OR VAPOR
 IN AIR, IN WHICH THE REACTION PROGRESSES THROUGH THE
 UNBURNED MATERIAL AT A RATE LESS THAN THE VELOCITY OF
 SOUND. A DEFLAGRATION CAN HAVE AN EXPLOSIVE EFFECT.
  
 PLEASE REVIEW FBC-B TABLE 414.5.1 EXPLOSION CONTROL
 REQUIREMENTS- COMBUSTIBLE DUST.
  
 2H) SCENE SHOP DOOR TYPE # 2, IS MISSING THE 12??? ON
 THE CORRIDOR SIDE ON THE LATCH SIDE OF DOOR. 2007 FBC-B
 11-4.13.6 MANEUVERING CLEARANCES AT DOORS.
  
 2I) THE TYPICAL STAIR DETAIL PROVIDED HAS ALL
 REFERENCES AND DIMENSIONS TO THE 2007 FBC-RESIDENTIAL
 CODE PLEASE UPDATE TO THE CORRECT CODE REFERENCES. THE
 DETAIL INDICATES THE USE OF ????? T & G FLOORING, NOTE
 TYPE I / TYPE II CONSTRUCTION FBC-B 1009.5 STAIRS ARE
 TO BE BUILT OF THE SAME MATERIALS WITH THE TYPE
 PERMITTED FOR THE TYPE OF CONSTRUCTION AS THE BUILDING
 TYPE.
  
 2J) PLEASE PROVIDE FLOOR AND FRAMING DETAILS FOR THE
 DJ???S RAISED FLOOR. FBC-B 603.1, FBC-B 1009.5 & FBC-B
 1009.1 HANDRAILS.
  
 2K) BOTH EXIT ACCESS CORRIDORS AND EXIT PASSAGE WAYS
 INDICATE THE USE OF CARPETED FLOORS, PLEASE COMPLY WITH
 FBC-B 804.4.1 MINIMUM CRITICAL RADIANT FLUX. INTERIOR
 FLOOR FINISH AND FLOOR COVERING MATERIALS IN EXIT
 ENCLOSURES, EXIT PASSAGEWAYS AND CORRIDORS SHALL NOT BE
 LESS THAN CLASS I IN GROUPS I-2 AND I-3 AND NOT LESS
 THAN CLASS II IN GROUPS A, B, E, H, I-4, M, R-1, R-2
 AND S. IN ALL AREAS, FLOOR COVERING MATERIALS SHALL
 COMPLY WITH THE DOC FF-1 "PILL TEST" (CPSC 16 CFR, PART
 1630).
  
 2L) PLANS WILL ALSO NEED TO SHOW COMPLIANCE WITH
 INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY
 OCCUPANCY FBC-B TABLE 803.5.
  
 3) SHEET A-2:
 3A) THE REHEARSAL STUDIO DOORS LABELED # 2 BOTH ARE
 MISSING THE REQUIRED 18??? PULL SIDE OF DOORS FBC-B
 11-4.13.6.
  
 3B) DRESSING ROOM DOORS LABELED # 2 BOTH ARE MISSING
 THE REQUIRED 18??? PULL SIDE OF DOORS FBC-B 11-4.13.6.
  
 3C) THE DESIGN CLASSROOM OUT SWING DOOR # 2 SWINGS OVER
 50% OF THE REQUIRED CORRIDOR WIDTH. FBC-B 1008.1.8.8.
  
 3D) THE PLANS INDICATE THE CORRIDORS TO BE RATED,
 PARTIALLY SEE STUDENT WORK ROOM?
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 3E) THE STUDENT WORK ROOM IS PART OF THE CORRIDOR AND
 ALSO INDICATES THE USE OF CARPET, PLEASE SHOW
 COMPLIANCE WITH 804.4.1 MINIMUM CRITICAL RADIANT FLUX.
 INTERIOR FLOOR FINISH AND FLOOR COVERING MATERIALS IN
 EXIT ENCLOSURES, EXIT PASSAGEWAYS AND CORRIDORS SHALL
 NOT BE LESS THAN CLASS I IN GROUPS I-2 AND I-3 AND NOT
 LESS THAN CLASS II IN GROUPS A, B, E, H, I-4, M, R-1,
 R-2 AND S. IN ALL AREAS, FLOOR COVERING MATERIALS SHALL
 COMPLY WITH THE DOC FF-1 "PILL TEST" (CPSC 16 CFR, PART
 1630).
  
 3F) THE PLANS INDICATE ELEVATOR DOORS BUT NO RATING,
 FBC-B TABLE 715.4.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  