Plan Review Notes
Plan Review Notes For Permit 10060024
Permit Number 10060024
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-06-02 15:06:49*****DENIED*****
  
 DRAWING 1 OF 1
  
 1) PROVIDE PIPE SIZES ON DRAWING FOR NODES 30, 36, 37 &
 38.
  
 2) PROVIDE SPRINKLER COVERAGE FOR WORK AREA LOCATED
 NEAR HYDRAULIC NODE 20.
  
 3) WAITING AREA AND SOUTH WORK AREA DOES NOT MEET THE
 DEFINITION OF A "SMALL ROOM"; THEREFORE, SPRINKLERS
 CANNOT BE LOCATED MORE THAN 7'-6" FROM WALLS.
  
 4) CONFIRM IF THE AQUAFLEX FLEXIBLE DROPS ARE BRAIDED
 OR UNBRAIDED AND WHICH SIZE (1/2" OR 3/4").
  
 5) FLEXIBLE SPRINKLER DROPS REQUIRE THE CEILING TO MEET
 ASTM C635/C636 AS MEDIUM OR HEAVY DUTY CEILING GRIDS.
  
 6) PROVIDE DETAIL SHOWING FLEXIBLE SPRINKLER ATTACHMENT
 TO CEILING GRID.
  
 7) PROVIDE ADDITIONAL INFORMATION ON ARMOVER DETAIL
 SHOWING MINIMUM BEND RADIUS/DIAMETER FOR FLEXIBLE
 DROPS.
  
  
 HYDRAULIC CALCULATIONS
  
 1) THE MINIMUM DISCHARGE PER SPRINKLER SHOULD BE 14.8
 GPM IF THE PRESSURE IS 7 PSI AND THE K-FACTOR IS 5.6.
  
 2) BALANCE THE SPRINKLER FLOWS; 7 PSI CANNOT BE USED AS
 THE HEAD PRESSURE FOR ALL SPRINKLERS.
  
 3) 250 GPM HOSE WAS ADDED TO THE CALCULATION BUT THE
 SYSTEM WAS CALCULATED AS LIGHT HAZARD.
  
 4) PROVIDE ADDITIONAL CALCULATION INFORMATION INCLUDING
 (PT), (PE) AND (PF) BETWEEN EACH NODE.
  
 6) PROVIDE HYDRAULIC INFORMATION FOR NODES 37-38.
  
 7) INCLUDE ARMOVER ELBOWS AND PIPING (SHOWN ON DETAIL)
 IN HYDRAULIC CALCULATIONS.
  
  
 CAPT. MICHAEL A. WILLIAMS
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6730