Plan Review Notes
Plan Review Notes For Permit 10060022
Permit Number 10060022
Review Stop E
Sequence Number 1
Notes
Date Text
2010-06-02 13:45:06 
 REVISION REQUIRED
  
 A DISCONNECT IS REQUIRED AT SEPARATE STRUCTURES PER
 225.31 & 225.32. GROUNDING ELECTRODE PER 250.32, LOCATE
 AND SIZE ON PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  