2010-06-24 13:36:48 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| 2007 FBC WITH 2009 REVISIONS. |
| |
| 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| UP. |
| |
| 2- ROOF SHEATHING UPLIFT AND ROOF-TO-WALL UPLIFT LOADS |
| SHALL BE INCREASED BY 20 PERCENT AS REQUIRED BY SEC. |
| R301.2.1.4.3(2). REVISE STRUCTURAL DRAWINGS AS REQUIRED |
| TO COMPLY WITH THIS SECTION. |
| |
| 3- SPECIFY THE DESIGN PRESSURES CALCULATED FOR THE |
| DOORS AND WINDOWS TO VERIFY COMPLIANCE WITH SEC. R301. |
| |
| 4- PROVIDE MANUFACTURER'S SPECIFICATIONS FOR ALL |
| COOKING EQUIPMENT SHOWING THAT THE EQUIPMENT WAS |
| DESIGNED TO BE INSTALLED ON THE PORCH A SHOWN ON PLANS. |
| |
| 5- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR NEW |
| FIREPLACE TO BE INSTALLED ON THE NEW PAVILION TO SHOW |
| COMPLIANCE WITH CHAPTER 10 OF 2007 FLORIDA RESIDENTIAL |
| CODE. |
| |
| 6- TIMBER STRUCTURAL DRAWINGS AND CALCULATIONS |
| SUBMITTED: |
| A) REVISE DESIGN CRITERIA TO COMPLY WITH THE 20% |
| INCREASED LOADS AS REQUIRED BY SEC. R301.2.1.4.3(2). |
| SEE ITEM # 2 ABOVE. |
| |
| B) REVISE DESIGN CRITERIA. EXPOSURE "D" IS NOT |
| APPLICABLE IN FLORIDA. SEE SEC. R301.2.1.4.3(3). |
| |
| C) ENGINEER (THOMAS R. BEAUDETTE) NEED TO USE CURRENT |
| FLORIDA ENGINEER'S SEAL. ENGINEER'S SEAL NEED TO SAY |
| "LICENSE" NOT "CERTIFICATE. THE SEAL WAS TO BE UTILIZED |
| PRIOR TO JANUARY 1, 2002. SEE SEC. 61G15-23.001 OF |
| FLORIDA ADMINISTRATIVE CODE AND SEC. 471.025 OF FLORIDA |
| STATUTE. |
| |
| D) ENGINEER OF RECORD (ALBERT A. GARGIULO) TO REVIEW |
| AND APPROVE ALL TIMBER DRAWINGS PRIOR TO SUBMITTAL TO |
| THIS OFFICE. |
| |
| 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A) WINDOW MULLIONS AS SHOWN ON PLANS. AND CLEARLY |
| SPECIFY MULLION SIZE AND FASTENERS TO VERIFY COMPLIANCE |
| WITH THE DESIGN PRESSURES REQUIRED BY SEC. R301. |
| |
| B) GLASS BLOCK AS SHOWN ON PLANS. |
| |
| C) PRECAST LINTELS AS SHOWN ON PLANS. |
| |
| 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY |
| AMENDMENTS TO FBC. |
| |
| 9- OWES $19.74 FOR RADON FEES AND LANDSCAPE REVIEW FEE. |
| |
| 10- SHEET A-2: REVISE TOP OF CHIMNEY CAP ELEVATION |
| SHOWN ON PARTIAL SOUTH ELEVATION. IT CAN'T BE 8'-2". |
| |