2010-06-21 16:40:412007 FBC W/2009 REVISIONS
 ADDITION
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) SUBMIT 2 COPIES OF A LOT DRAINAGE PLAN COMPLYING
 WITH FBC R401.3.
  
 3) ON SHEETS A1 AND A2 THE EXPOSURE CATEGORY IS
 INCORRECTLY SPECIFIED AS B. BECAUSE THE STRUCTURE IS
 LOCATED WITHIN 1500 FEET OF THE INTRA COASTAL WATERWAY
 THE CORRECT EXPOSURE IS CATEGORY C. PLEASE CORRECT THE
 PLANS AND REVISE THE WINDLOAD PRESSURES ACCORDINGLY.
 FBC R 301
  
 4) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS FBC 106.3.3
  
 5) PLEASE REVIEW WALL REINFORCEMENT AND BRACING FOR
 GABLE END AT THE CATHEDRAL CEILING. SEE FBC R609.4.
  