Plan Review Notes For Permit 10050791 |
Permit Number |
10050791 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-06-25 14:58:28 | *****DENIED***** | | | | | | 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK | | OF EACH SUBMITTED PLAN SHEET. | | | | 2. THE GATE SHALL BE INSTALLED WITH A KNOX GATE ENTRY | | KEY SWITCH FOR EMERGENCY FIRE ACCESS. AMEND NOTE 4 ON | | A200.OR DRAWING. | | | | 3. IN ADDITION TO ADDRESS NUMBER SHOWN ON THE GATE AS | | BEING AT LEAST 6" IN HEIGHT, WEST PALM BEACH CODE ALSO | | REQUIRES THAT ADDRESS NUMBERS SHALL BE AT LEAST 1" IN | | WIDTH. | | | | 4. VERIFY (IF ANY) THAT THE STRUCTURE'S OVERHANG DOES | | NOT IMPEDE THE MINIMUM VERTICAL CLEARANCE OF 13' 6" | | REQUIRED FOR FIRE EMERGENCY APPARATUS. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|