Plan Review Notes For Permit 10050733 |
Permit Number |
10050733 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-06-03 14:04:19 | *****DENIED***** | | | | | | 1. SINCE THE PROJECT SCOPE OF WORK IS IN THREE (3) | | DISTINCT SUITES, PLEASE IDENTIFY THE SUITES ON THE | | FLOOR PLAN FOR LOCATION PURPOSES. | | | | 2. PLEASE PROVIDE PRESCRIPTIVE STRENGTHS OF THE | | HANDRAILS/GUARDRAILS FOR THE NEW METAL PAN STAIR. | | | | 3. ON SHEET A-3.0, UNDER INTERIOR FINISH SCHEDULE, | | PLEASE EXPLAIN NOTATION ** REMAINDER OF SUITE 217 & 222 | | TO RECEIVE NEW CARPET, VINYL BASE AND PAINT. | | | | 4. ON SHEET E3.1, THERE APPEARS TO BE A LACK OF FIRE | | ALARM DEVICES (STROBES, AUDIBLE STROBES) I.E. NO | | STROBES SHOWN IN THE RESTROOM. | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|