2010-05-26 09:52:54RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ENGINEER CALCULATIONS SUBMITTED DON'T COMPLY WITH
 SEC. 8.1 OF ROOFING APPLICATION STANDARD (RAS) 117. THE
 MINIMUM FASTENER SEPARATION SHALL NOT BE LESS THAN 4
 IN. O.C.. ENGINEER CALCULATIONS SHOW 3 IN O.C. SPACING
 FOR ROOF CORNER AREAS. REVISE AS REQUIRED.
  
 2- ENGINEER FASTENING SPACING FOR PERIMETER AREA
 SPECIFIES SIDE LAP FASTENER SPACING AT 12 IN. O.C.
 PRODUCT APPROVAL (NOA 09-0224.01) SUBMITTED SPECIFIES
 SIDE LAP SPACING AT 9 IN. O.C. FOR FIELD AREA ONLY.
 REVISE SIDE LAP SPACING FOR PERIMETER AREA AND PROVIDE
 SIDE LAP NAIL ENHANCING AT PERIMETER AND CORNER AREAS
 ACCORDINGLY TO RAS 117 CALCULATIONS.
  
 3- ENGINEER TO PROVIDE ALL HIS INFORMATION AND
 ENGINEERING FIRM CERTIFICATE OF AUTHORIZATION NUMBER AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTES AND BY SEC.
 61G15-23.002(2) OF FLORIDA ADMINISTRATIVE CODE. NO
 INFORMATION WAS SUBMITTED.
  