Plan Review Notes
Plan Review Notes For Permit 10050628
Permit Number 10050628
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-06-08 16:49:58*****DENIED*****
  
  
 1. THE ADDRESS NUMBER LISTED IN THE TITLE BLOCK OF THE
 PLANS (6405) DOES NOT CORRELATE WITH THE ADDRESS NUMBER
 (6505) LISTED ON THE PERMIT APPLICATION. THE ACTUAL
 PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET.
  
 2. WHAT WAS THE PREVIOUS OCCUPANCY TYPE?
  
 3. THE PERMIT APPLICATION INDICATES THAT THE PROJECT
 SCOPE OF WORK WILL BE IN SUITE 101 WHICH ENTAILS THAT
 THERE ARE ADDITIONAL TENANT SPACES UNDER THE BUILDING
 ADDRESS OF 6505 SOUTH DIXIE HIGHWAY. PLEASE VERIFY AND
 ADVISE.
  
 4. SPECIFY THE INTERIOR FINISH FOR WALLS AND CEILING IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 5. ON SHEET 6.1, THE 2003 EDITION OF NFPA 101 IS
 INCORRECTLY REFERENCED. THIS SHOULD BE THE 2006 EDITION
 AS CORRECTLY LISTED ON 1.1 SHEET.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722