Plan Review Notes For Permit 10050628 |
Permit Number |
10050628 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-06-09 14:02:34 | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008 | | NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED, | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE REFERENCED CODES ON SHEET 6.1 ARE INCORRECT, SEE | | CODES REFERENCED ABOVE AND IN THE 2007 FBC. | | | | 2} THE LOAD CALCULATION USED IS FOR DWELLING UNITS, SEE | | ARTICLE 220.10, 220.14 AND ALL APPLICABLE SECTIONS OF | | THAT ARTICLE. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|