 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE REFERENCED CODES ON SHEET 6.1 ARE INCORRECT, SEE
 CODES REFERENCED ABOVE AND IN THE 2007 FBC.
  
 2} THE LOAD CALCULATION USED IS FOR DWELLING UNITS, SEE
 ARTICLE 220.10, 220.14 AND ALL APPLICABLE SECTIONS OF
 THAT ARTICLE.
  