2010-05-24 11:58:25RESIDENTIAL (R2) RE-ROOF, BUILDING REVIEW CHECKLIST:
  
 1- THERE ARE TWO DIFFERENT ASSEMBLIES SUBMITTED. ONE IS
 ON PAGE 7 OF 14 AND THE OTHER ONE IS ON PAGE 9 OF 14.
 ENGINEERING CALCULATIONS ONLY SPECIFY SYSTEM ON PAGE 7
 OF 14. ALSO, THERE ARE SOME HAND WRITTEN CALCULATIONS
 ON SHEET 9 OF 14. THESE CALCULATIONS ARE INCORRECT
 BECAUSE THIS BUILDING IS LOCATED ON EXPOSURE "C". NEED
 TO REVISE ENGINEERING CALCULATIONS TO REFLECT
 INFORMATION SUBMITTED. PROVIDE CALCULATIONS WITH
 ENGINEER'S ORIGINAL SEAL AND SIGNATURE TO FILE ON
 MASTER PERMIT..
  
 2- REMAINDER: NEED THE TESTING APPLICATION STANDARD TAS
 105 AS REQUIRED BY CONCRETE DECK SYSTEM LIMITATION ON
 LAST PAGE OF NOA SUBMITTED.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER