Plan Review Notes For Permit 10050602 |
Permit Number |
10050602 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-05-24 11:58:25 | RESIDENTIAL (R2) RE-ROOF, BUILDING REVIEW CHECKLIST: | | | | 1- THERE ARE TWO DIFFERENT ASSEMBLIES SUBMITTED. ONE IS | | ON PAGE 7 OF 14 AND THE OTHER ONE IS ON PAGE 9 OF 14. | | ENGINEERING CALCULATIONS ONLY SPECIFY SYSTEM ON PAGE 7 | | OF 14. ALSO, THERE ARE SOME HAND WRITTEN CALCULATIONS | | ON SHEET 9 OF 14. THESE CALCULATIONS ARE INCORRECT | | BECAUSE THIS BUILDING IS LOCATED ON EXPOSURE "C". NEED | | TO REVISE ENGINEERING CALCULATIONS TO REFLECT | | INFORMATION SUBMITTED. PROVIDE CALCULATIONS WITH | | ENGINEER'S ORIGINAL SEAL AND SIGNATURE TO FILE ON | | MASTER PERMIT.. | | | | 2- REMAINDER: NEED THE TESTING APPLICATION STANDARD TAS | | 105 AS REQUIRED BY CONCRETE DECK SYSTEM LIMITATION ON | | LAST PAGE OF NOA SUBMITTED. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|