Plan Review Notes For Permit 10050482 |
Permit Number |
10050482 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-08-16 11:35:29 | 2007 FBC W/2009 REVISIONS | | | | MECHANICAL REVISIONS REQUIRED. | | | | 1) THE ENERGY CALCULATION COVERSHEET APPEARS TO BE | | USING THE WHOLE HOUSE METHOD TO SHOW COMPLIANCE BY | | LISTING THE CONDITIONED AREA AS 3976 SQFT. IN ORDER TO | | USE THIS METHOD THE WHOLE BUILDING ENVELOPE AND ALL OF | | ITS MAJOR ENERGY CONSUMING SYSTEMS ARE REQUIRED TO BE | | CALCULATED AND COMPARED TO A BASELINE HOUSE OF THE SAME | | CONFIGURATION. HOWEVER, ONLY TWO HVAC SYSTEMS ARE | | SPECIFIED, A 12K AND AN 18K. THE FORM 1100A-08 LISTS | | THE COOLING SYSTEMS CAPACITY AS 41.2 K BTUH AND THE | | MANUAL J CALCS. SPECIFIES 32,539 BTUH FOR THE 592 SQFT | | OF ADDED SPACE. PLEASE COORDINATE THE CALCULATIONS, | | FORMS AND PLANS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|