Plan Review Notes
Plan Review Notes For Permit 10050482
Permit Number 10050482
Review Stop M
Sequence Number 1
Notes
Date Text
2010-06-08 09:26:382007 FBC W/2009 REVISIONS
 ADDITION AND REMODEL
  
 DENIED BY MECHANICAL
  
 1) THE A/C UNIT SIZES SPECIFIED ON THE ENERGY
 CALCULATION FORM DOES NOT MATCH THE PLANS. THE PLANS
 SPECIFIES A 17,000 BTU COOLING WITH A 14.7 SEER AND THE
 ENERGY CALCS. LISTS A 12,000 BTU WITH A 17.8 SEER.
 PLEASE COORDINATE THE ENERGY CALCULATIONS AND EQUIPMENT
 SIZING CALCULATIONS WITH THE PLANS AND MAKE REQUIRED
 CORRECTIONS. FBC R M1401
  
 2) MECHANICAL EQUIPMENT TO BE LOCATED AT A MINIMUM OF
 7.5 FEET BASE FLOOD ELEVATION. FBC R M1401.5
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW