2010-06-08 14:31:08 | 2007 FBC W/2009 REVISIONS |
| ADDITION AND REMODEL |
| |
| DENIED BY BUILDING |
| |
| 1) THE PROJECT IS LOCATED IN AN A5 FLOOD ZONE WITH A |
| BASE FLOOD ELEVATION OF 7 FEET. THE CITY OF WEST PALM |
| BEACH MUNICIPAL CODE ARTICLE XVII SECTION 94-546 |
| REQUIRES ALL NEW RESIDENTIAL CONSTRUCTION OR |
| SUBSTANTIAL IMPROVEMENT OF ANY EXISTING RESIDENTIAL |
| STRUCTURE TO HAVE THE LOWEST FLOOR ELEVATED TO SIX |
| INCHES ABOVE THE BASE FLOOD ELEVATION. THIS REQUIREMENT |
| ALSO APPLIES TO ALL SYSTEMS THAT SUPPLY THE STRUCTURE |
| SUCH AS A/C EQUIPMENT. PROVIDE ELEVATIONS ON DRAWINGS |
| THAT SHOW COMPLIANCE. |
| |
| 2) PROVIDE TWO COPIES OF A SURVEY. |
| |
| 3) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C AND |
| WITHIN 600 FEET OF THE INTRACOASTAL WATERWAY. SECTION |
| FBC R301.2.1.4.3 (2) OF THE 2009 REVISIONS TO THE 2007 |
| FBC REQUIRES THE ROOF SHEATHING UPLIFT AND THE ROOF TO |
| WALL UPLIFT LOADS TO BE INCREASED BY 20 PERCENT. SHOW |
| COMPLIANCE. |
| |
| 4) THE PLANS WILL BE REQUIRED TO BE REVIEWED BY PALM |
| BEACH COUNTY FOR IMPACT FEES AND A COPY OF THE PAID |
| RECEIPT SUBMITTED BEFORE THE PERMIT IS ISSUED. |
| |
| 5) THERE HAVE BEEN SOME HANDWRITTEN CHANGES MADE TO |
| SHEETS A101 AND A103 OF THE PLANS. HANDWRITTEN CHANGES |
| TO SIGNED AND SEALED PLANS ARE NOT ALLOWED EXCEPT BY |
| THE ARCHITECT OR ENGINEER. FS 471 AND 481. |
| |
| 6) PLEASE UPDATE THE CODE EDITION ON SHEETS S-0 AND S-4 |
| TO THE 2007 FBC W/2009 REVISIONS AND ASCE 7-05. ALSO |
| SPECIFY THE 2005 EDITIONS OF ACI 318 AND 530 PER |
| CHAPTER 43 OF FBC RESIDENTIAL. |
| |
| 7) COORDINATE THE REVISED ARCHITECTURAL DIMENSIONS OF |
| THE PORCH ADDITION WITH THE STRUCTURAL DRAWINGS. |
| |
| 8) SHOW COMPLIANCE WITH FBC R320.7 WHICH REQUIRES |
| GUTTERS WITH DOWNSPOUTS AT THE NEW PORCH ADDITION WITH |
| EAVES OF LESS THAN 6 INCHES OF HORIZONTAL PROJECTION. |
| |
| 9) PLEASE CORRECT THE WINDOW SCHEDULE ID MARKS ON A103. |
| THEY SHOULD BE W01 AND W02. |
| |
| 10) THE WINDOW AND DOOR PRESSURES ON S-4 APPEAR TO BE |
| LOW. PLEASE REVIEW AND PROVIDE CALCULATIONS. |
| |
| 11) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| SPECIFICATIONS OR EVALUATION REPORTS FOR THE SPRAY FOAM |
| INSULATION. |
| |
| 12) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| STRUCTURAL MULLIONS AS REQUIRED BY DCA RULE 9B-72. |
| |
| 13) PLEASE SPECIFY THE APPROVED ASSEMBLY, FASTENING |
| OPTION AND THE DESIGN PRESSURE FOR THE TAMKO MODIFIED |
| ROOF SYSTEM. SUBMIT TWO COPIES OF RAS 117 CALCULATIONS |
| FOR ENHANCED UPLIFT AT THE PERIMETER AND CORNERS AS |
| REQUIRED BY THE GENERAL LIMITATIONS ON PAGE 18 OF THE |
| NOA. |
| |