Plan Review Notes
Plan Review Notes For Permit 10050267
Permit Number 10050267
Review Stop P
Sequence Number 1
Notes
Date Text
2010-06-02 17:03:232007 FBC W/2009 REVISIONS
 ADDITION
  
 DENIED BY PLUMBING
  
 1) THE 2" HORIZONTAL DRY VENT FOR THE WATER CLOSET
 SHOWN ON THE SANITARY ISOMETRIC ON SHEET 14 IS NOT
 ALLOWED. FBC R P3104.4 REQUIRES EVERY DRY VENT TO RISE
 VERTICALLY TO A MINIMUM OF 6" ABOVE THE FLOOD LEVEL OF
 THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.
  
 2) FBC R P3005.2.6 REQUIRES AN ACCESSIBLE CLEANOUT AT
 THE BASE OF EACH VERTICAL WASTE OR SOIL STACK. SHOW
 CLEANOUT AT BASE OF SOIL STACK FROM THE SECOND FLOOR ON
 ISOMETRIC.
  
 3) THE WATER ISOMETRIC GOES FROM 3/4" TO 1" TO 3/4" ON
 THE HOT WATER JUST PAST THE TANKLESS HEATER. THIS
 APPEARS TO BE AN ERROR. PLEASE REVIEW.
  