Plan Review Notes For Permit 10050267 |
Permit Number |
10050267 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-06-03 09:09:45 | 2007 FBC W/2009 REVISIONS | | ADDITION | | | | DENIED BY MECHANICAL | | | | 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT | | SIZING CALCULATIONS FOR THE ADDITION AS REQUIRED BY FBC | | R M1401.3. THE EQUIPMENT SPECIFIED ON THE PLANS MUST | | CORRESPOND WITH THE CALCULATIONS. | | | | 2) THE ATTIC ACCESS OPENING IS REQUIRED TO BE WITHIN 6 | | FT OF THE AIR HANDLER AND SHALL MEET ALL REQUIREMENTS | | OF FBC R M1305.1.3. | | | | 3) PROVIDE CALCULATIONS OR OTHER DOCUMENTATION THAT THE | | MECHANICAL EQUIPMENT THAT IS EXPOSED TO WIND IS | | DESIGNED AND INSTALLED TO RESIST WIND PRESSURES AS | | REQUIRED BY FBC R M1307.3. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|