| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 |
| REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE |
| SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED. |
| |
| THESE COMMENTS RELATE TO SHEET 14: |
| |
| 1} NOTE #17 IS INCOMPLETE. SEE 210.12 NEC 2008 FOR ARC |
| FAULT LOCATIONS, CHANGE NOTE TO REFLECT SAME. ALSO |
| SEE406.11 FOR TAMPER RESISTANT RECEPTACLE REQUIREMENTS. |
| |
| 2} THE EQUIPMENT GROUND BETWEEN THE METER AND |
| DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH |
| TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN |
| ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN |
| FROM THE FIRST MEANS OF DISCONNECT. 250.6. |
| |
| |
| 3} A GROUNDING ELECTRODE CONDUCTOR IS REQUIRED SIZED |
| PER 250.66. INDICATE LOCATION AND SIZE ON THE RISER. |
| |
| 4} THE AIR HANDLER CIRCUIT 27 & 29 ON THE PANEL |
| SCHEDULE (35 AMPS) DOES NOT CORRELATE WITH THE A/C |
| SCHEDULE MOCP (20) .408.4. |
| |
| THESE COMMENTS RELATE TO SHEET 11 |
| |
| 6} LABEL ALL ROOMS FOR CLARITY, RECORD RETENTION AND SO |
| OUTLET REQUIREMENTS OF 210.52 CAN BE REVIEWED. |
| |
| 7} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2 |
| RESIDENTIAL FLORIDA BUILDING CODE. INDICATE LOCATION ON |
| PLANS, SEE R313.4 FOR CARBOBON MONOXIDE DETECTION |
| REQUIREMENTS. |
| |
| 8} VERIFY FAN CIRCUIT NUMBER IN UPPERBEDROOM. M16 IS |
| LABELED "SPARE" ON THE SCHEDULE AND M15 WOULD BE IN |
| VIOLATION OF 210.11(C)(3). |
| |
| 9} THE DISCONNECT FOR CU #2 IS IN VIOLATION OF WORKING |
| SPACE CLEARANCE 110.26. |
| |
| NOTE THE GENERATER SHOWN ON SHEET 11 REQUIRES A |
| SEPARATE PERMI WITH PLANS AND SPECIFICATIONS. ALSO A |
| SURVEY ONDICATING SETBACKS. |
| |