2010-06-30 17:18:16RESIDENTIAL (R3) REPAIRS/ ADDITION BUILDING REVIEW
 CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- A) PER DISCUSSION WITH BUILDING OFFICIAL, CONTRACTOR
 TO PROVIDE SIGNED CONSTRUCTION CONTRACT SHOWING FEE
 BREAKDOWN FOR EACH SCOPE OF WORK TO BE PERFORMED. EG:
 FEES TO RECONSTRUCT EXISTING FLORIDA ROOM AND TO
 REPLACE ROOF AS CITED ON THE HEALTH AND SAFETY
 VIOLATION. AND, FEES FOR THE PROPOSED IMPROVEMENTS
 (REPLACE DOORS, WINDOWS, BATHTUB, ETC.).
  
 ***NOTE: PLEASE MAKE SURE NUMBERS SHOWN ON CONTRACT
 MATCH NUMBERS SHOWN ON PERMIT APPLICATION.
  
 2- A) PRODUCT APPROVAL FOR STEEL DOOR NOA 08-1015.05 IS
 MISSING THE DRAWINGS. PROVIDE THE DRAWINGS.
 B) CLARIFY IF USING STEEL DOOR NOA 08-0208.07 OR NOT.
 ENGINEER OF RECORD DIDN'T LIST THIS NOA AS PART OF THE
 REVIEWED PRODUCT APPROVALS.
  
 3- ROOFING PRODUCT APPROVAL NOA 07-0802.09: CLEARLY
 MARK WHICH APPROVED SYSTEM IS GOING TO BE USED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 4- STORM SHUTTERS: INFORMATION SHOWN ON SHUTTER
 MOUNTING DETAIL ON ENGINEER'S DRAWING #1 DOESN'T MATCH
 INFORMATION SHOWN ON THE SHUTTERS INSTALLATION
 SCHEDULE. COORDINATE INFORMATION TO MATCH. EG: REVISE
 THE DESIGN PRESSURES TO MATCH DESIGN PRESSURES SHOWN ON
 DRAWING #2. REVISE THE MINIMUM EDGE DISTANCE TO MATCH
 ALSO.
  
 5- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 6- ENERGY CALCULATIONS SUBMITTED:
 A) NEED TO PROVIDE CURRENT REVISED FORM. USE FORM
 1100B-08 NOT 1100B-07.
 B) COMPLETE ALL THE INFORMATION ON TOP OF FORM
 INCLUDING BUILDER AND OWNER INFORMATION.
 C) REVISE ITEM #8. SEE PLANS FOR TOTAL SLAB ON GRADE
 LINEAR FEET. 24 LINEAR FEET IS INCORRECT.
  
 7- TRUSS PACKAGE SUBMITTED:
 A) TRUSSES NEED TO BE REVISED FOR EXPOSURE "C", NOT
 EXPOSURE "B". REVISE AS REQUIRED. SEE PLANS.
  
 B) TRUSS PACKAGE IS NOT COMPLYING WITH SEC F.A.C.
 CHAPTER 61G15-31.003. MISSING THE TRUSS ENGINEER
 INFORMATION ON EACH SHEET.
  
 C) CLARIFY WHY TRUSS ENGINEER SIGNED AND SEALED
 DOCUMENTS ON 12/13/10?
  
 D) ENGINEER OF RECORD TO REVIEW AND APPROVE TRUSS
 PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712