2010-05-25 14:11:10 | RESIDENTIAL (R3) REPAIRS/ADDITION BUILDING REVIEW |
| CHECKLIST. |
| 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| |
| 1- PER DISCUSSION WITH BUILDING OFFICIAL, CONTRACTOR TO |
| PROVIDE SIGNED CONSTRUCTION CONTRACT SHOWING FEE |
| BREAKDOWN FOR EACH SCOPE OF WORK TO BE PERFORMED. EG: |
| FEES TO RECONSTRUCT EXISTING FLORIDA ROOM. FEES TO |
| REROOF HOUSE. FEES TO REPLACE DOORS, WINDOWS, BATHTUB, |
| ETC. THIS INFORMATION IS REQUIRED TO IDENTIFY |
| "SUBSTANTIALLY IMPROVEMENTS" OR "IMPROVEMENTS OF A |
| STRUCTURE" TO COMPLY WITH EXISTING HEALTH, SANITARY, OR |
| SAFETY CODES WHICH ARE NECESSARY TO ENSURE SAFE LIVING |
| CONDITIONS. SEE SUBSTANTIAL IMPROVEMENTS DEFINITION ON |
| CITY ORDINANCES SEC. 94-611 TO COMPLY WITH THE CITY |
| FLOODPLAIN MANAGEMENT POLICY. |
| |
| 2- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A) CONCRETE ROOF TILE AND ADHESIVE TO BE USED. IF USING |
| SCREWS/NAILS SPECIFY HOW MANY AND TYPE TO VERIFY |
| COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301. |
| B) EXTERIOR DOORS TO BE REPLACED. |
| C) WINDOWS TO BE REPLACED. |
| D) WINDOW MULLIONS. AND CLEARLY MARK SPECIFIC MULLION |
| SIZE AND FASTENING TO VERIFY DESIGN PRESSURES OF SEC. |
| R301. |
| E) STORM SHUTTERS AND COMPLETE INSTALLATION SCHEDULE. |
| F) TRUSS CONNECTORS AS SPECIFIED ON PLANS. |
| |
| 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| |
| 4- OWES $0.62 FOR RADON FEES FOR NEW PORCH. |
| |
| 5- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| UP. |
| |
| 6- PROJECT NOTES ON SHEET 1: |
| A) SPECIFY ASCE 7-05 NOT ASCE 7-02. |
| B) SPECIFY ROOF DEAD LOADS ALSO AS REQUIRED BY SEC. |
| R301.1 OF 2007 FLORIDA RESIDENTIAL CODE. ONLY THE ROOF |
| LIVE LOADS WHERE SPECIFIED. |
| |
| 7- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| N1100.3 OF CHAPTER 11. |
| |