2010-06-10 14:07:49 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO |
| THE 2007 FLORIDA RESIDENTIAL CODE, THIS BUILDING IS |
| LOCATED ON EXPOSURE "C" NOT "B". REVISE THE OPENING |
| DESIGN PRESSURES ON SHEET S1 TO REFLECT EXPOSURE "C". |
| |
| 2- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A) ROOF TILE TO BE INSTALLED. |
| B) ROOF TILE ADHESIVE IF USING ADHESIVE FOR TILE |
| INSTALLATION. SEE TILE PRODUCT APPROVAL FOR LISTED |
| ADHESIVES. SPECIFY HOW ARE TILES GOING TO BE INSTALLED. |
| C) FLAT ROOF TO BE INSTALLED AND, |
| * CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY AND BASE |
| SHEET FASTENING OPTION IS GOING TO BE USED TO VERIFY |
| COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301. |
| ** PROVIDE NAIL ENHANCING FOR PERIMETER AND CORNER |
| AREAS AS REQUIRED BY GENERAL LIMITATION #7. SEE LAST |
| PAGE OF NOA SUBMITTED. IF RAS 117 CALCULATIONS ARE |
| REQUIRED TO BE SIGNED AND SEALED, THEN PROVIDE SIGNED |
| AND SEALED RAS 117 CALCULATIONS. SEE LAST PAGE OF NOA |
| SUBMITTED. |
| NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION |
| #9 CAN'T BE USED IN THIS BUILDING BECAUSE THEY DON'T |
| MEET THE DESIGN PRESSURES OF SEC. R301. |
| D) FRENCH DOOR: FRENCH DOOR NOA 07-0103.02 SUBMITTED |
| EXPIRED ON FEBRUARY 24, 2010. NEED TO PROVIDE CURRENT |
| NOA. |
| |
| 3- ARCHITECT TO REVIEW AND APPROVE ALL PRODUCT |
| APPROVALS IN WRITING (NOT SIGNING AND SEALING) AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| |
| 4- ARCHITECT TO SPECIFY ROOF VENTILATION AS REQUIRED BY |
| SEC. R806 OF 2007 FLORIDA RESIDENTIAL CODE. |
| |
| 5- REVISE SHEET A3 TO OMIT WORK ON PORCH ROOF. |
| |
| 6- SHEET S3: ROOF FRAMING DETAIL #3 AND SECOND FLOOR |
| FRAMING DETAIL #2 WERE REVISED AND NOW THEY ARE MISSING |
| THE WOOD FRAMING MEMBERS. MISSING THE TOP AND BOTTOM |
| PLATES. |
| |
| 7- REVISE STUCCO THICKNESS ON BUILDING SECTION #1 ON |
| SHEET A2 AND NOTE S7 ON SHEET S2. |