2010-05-18 16:22:44 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| |
| 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO |
| THE 2007 FLORIDA RESIDENTIAL CODE, THIS BUILDING IS |
| LOCATED ON EXPOSURE "C" NOT "B". REVISE WIND DESIGN |
| CRITERIA AND THE OPENING DESIGN PRESSURES ON SHEET S1. |
| |
| 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| UP. |
| |
| 3- PROVIDE COPY OF THE PAID IMPACT FEES RECEIPT. |
| |
| 4- OWES $2093.06. PERMIT FEE BALANCE. |
| |
| 5- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A) ROOF TILE TO BE INSTALLED. |
| |
| B) ROOF TILE ADHESIVE IF USING ADHESIVE FOR TILE |
| INSTALLATION. SEE TILE PRODUCT APPROVAL FOR LISTED |
| ADHESIVES. |
| |
| C) FLAT ROOF TO BE INSTALLED AND, |
| * CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY AND BASE |
| SHEET FASTENING OPTION IS GOING TO BE USED TO VERIFY |
| COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301. |
| ** PROVIDE NAIL ENHANCING FOR PERIMETER AND CORNER |
| AREAS AS REQUIRED BY GENERAL LIMITATION #7. SEE LAST |
| PAGE OF NOA SUBMITTED. IF RAS 117 CALCULATIONS ARE |
| REQUIRED TO BE SIGNED AND SEALED, THEN PROVIDE SIGNED |
| AND SEALED RAS 117 CALCULATIONS. SEE LAST PAGE OF NOA |
| SUBMITTED. |
| NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION |
| #9 CAN'T BE USED IN THIS BUILDING BECAUSE THEY DON'T |
| MEET THE DESIGN PRESSURES OF SEC. R301. |
| |
| D) FRENCH DOOR WITH TRANSOM ABOVE AS SHOWN ON PLANS. |
| |
| 6- ARCHITECT TO REVIEW AND APPROVE ALL PRODUCT |
| APPROVALS IN WRITING (NOT SIGNING AND SEALING) AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. THIS |
| APPLIES TO NEW PRODUCT APPROVALS THAT WERE MISSING WITH |
| THIS SUBMITTAL. |
| |
| 7- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806 OF |
| 2007 FLORIDA RESIDENTIAL CODE. |
| |
| ***NOTE: COORDINATE WITH INFORMATION SHOWN ON THE |
| ENERGY CALCULATIONS. ENERGY CALCULATIONS SHOW VENTED |
| ATTIC. |
| |
| 8- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| FOR CANVAS ROOF TO BE REMOVED FOR NEW CONCRETE TILE TO |
| BE INSTALLED. |
| |
| 9- CLEARLY COORDINATE TRUSS CONNECTOR SCHEDULE WITH |
| FRAMING PLANS TO VERIFY COMPLIANCE WITH THE DESIGN |
| LOADS OF SEC. R301.. FRAMING PLANS DON'T SPECIFY ANY |
| CONNECTORS. |
| ALSO, COORDINATE TRUSS CONNECTOR SCHEDULE WITH THE |
| CONNECTORS SPECIFIED ON DETAILS SHOWN ON SHEET S3. EG: |
| DETAIL #2 SPECIFIES SIMPSON HETA24. THIS IS A MASONRY |
| EMBEDDED CONNECTOR. NEED TO SPECIFY WOOD TO WOOD |
| CONNECTOR. REVISE AS REQUIRED. |
| |
| 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| BALCONY GUARDRAIL TO SHOW COMPLIANCE WITH TABLE R301.5 |
| AND SEC. R312. |
| |
| 11- A) ENERGY CALCULATIONS TO BE SIGNED AND DATED BY |
| THE OWNER/AGENT. |
| |
| B) COORDINATE INFORMATION ON ENERGY CALCULATIONS WITH |
| INFORMATION GIVEN ON THE PLANS SUBMITTED. EG: CHECK |
| ROOF VENTILATION, ETC. SEE ITEM #7 ABOVE. |
| |
| 12- SHEET A0: |
| A) REVISE CITED CODE. CURRENT CODE IS 2007 FLORIDA |
| RESIDENTIAL CODE WITH 2009 REVISIONS NOT 2004 CODE. |
| |
| B) REVISE LEVEL OF ALTERATION. THIS IS NOT A LEVEL ONE |
| ALTERATION. SEE CHAPTER 4 OF THE 2007 EXISTING BUILDING |
| CODE TO PROPERLY CLASSIFIED ALTERATION LEVEL AND REVISE |
| AS REQUIRED. |
| |
| 13- REVISE THICKNESS OF STUCCO SPECIFIED ON ALL DETAILS |
| AND SPECIFICATIONS. EXTERIOR STUCCO TO BE 7/8" AS |
| REQUIRED BY TABLE R702.1(1). |
| |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561)805-6712 |