2010-04-29 15:28:52REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. SCOPE OF WORK NOT CLEAR. THE APPLICATION STATES
 ???REINSTALL A PAINT MIX ROOM AT NEW LOCATION,??? BUT I
 WAS UNABLE TO FIND RECORD OF A PAINT MIXING ROOM AT
 THIS ADDRESS. FBC106. PLANS SHOW A NEW PAINT BOOTH.
 PROJECT DESCRIPTION SHOULD BE CONSISTENT WITH PLANS.
  
 2. PROVIDE A SITE PLAN WHICH SHOWS BUILDING IN RELATION
 TO THE LOT LINES; SEE EXHAUST REQUIREMENTS, FBC M501.2,
 FBC M501.2.1.
  
 3. SHOW THE DISTANCE BETWEEN THE EXHAUST AND INTAKE,
 FBC M501.2.1.
  
 4. FBC M607.5, EXHAUST THROUGH A 2 HOUR EXTERIOR WALL
 IS SHOWN. PLEASE ADDRESS.
  
 5. CODE INFORMATION PROVIDES INFORMATION REGARDING
 AMOUNTS OF PAINT PERMITTED WITHIN 6FT OF THE SPRAY
 AREA. PLEASE EXPLAIN, WHERE IS THE SPRAY AREA? WHERE
 WILL THE PAINT BE STORED, AND IN WHAT QUANTITIES, FBC
 M502.8.1? SEE FBC M 502.7, PAINT SPRAY REQUIREMENTS, IF
 THIS IS EXISTING, HOW DO EXISTING EXHAUST AND INTAKE
 OPENINGS AFFECT THE PROPOSED OPENINGS?
  
 6. A 2 HOUR INTERIOR WALL IS SHOWN, IS THIS EXISTING OR
 PROPOSED? FBC 106.
  
 7. A 2 HR FIRE RATED WALL IS SHOWN WITH NO DOOR, IS
 THIS CORRECT? A 24X24 OPENING IS SHOWN, PRESUMABLY FOR
 MAKEUP AIR. A DOOR WOULD INHIBIT THE FLOW OF MAKEUP
 AIR, BUT AN UNPROTECTED DOOR SIZED OPENING WOULD AFFECT
 THE FIRE RESISTANCE OF THE 2 HOUR WALL. PLEASE REVISE
 PLAN TO SHOW COMPLIANCE WITH FBC M502.9.5.4, MAKEUP
 AIR.
  