2010-05-12 16:22:18 | BUILDING PLAN REVIEW |
| PERMIT: 10040630 |
| ADD: 6312 GEORGIA AVE |
| CONT: SHARKEY'S AIR |
| TEL: (941)625-2143 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION INDICATES THE PAINT MIX BOOTH |
| IS TO BE RE-INSTALLED AT THIS LOCATION. THE CITY'S |
| RECORDS DO NOT INDICATE ANY PERMITTED SPRAY BOOTH NOR |
| FIRE SUPRESSION SYSTEMS. |
| PLEASE PROVIDE ADDITIONAL INFORMATION ON THE FOLLOWING: |
| |
| F] 416.1 GENERAL. THE PROVISIONS OF THIS SECTION SHALL |
| APPLY TO THE CONSTRUCTION, INSTALLATION AND USE OF |
| BUILDINGS AND STRUCTURES, OR PARTS THEREOF, FOR THE |
| SPRAYING OF FLAMMABLE PAINTS, VARNISHES AND LACQUERS OR |
| OTHER FLAMMABLE MATERIALS OR MIXTURES OR COMPOUNDS USED |
| FOR PAINTING, VARNISHING, STAINING OR SIMILAR PURPOSES. |
| SUCH CONSTRUCTION AND EQUIPMENT SHALL COMPLY WITH THE |
| FLORIDA FIRE PREVENTION CODE. |
| |
| |
| F] 416.2 SPRAY ROOMS. SPRAY ROOMS SHALL BE ENCLOSED |
| WITH FIRE BARRIERS WITH NOT LESS THAN A 1-HOUR |
| FIRE-RESISTANCE RATING. FLOORS SHALL BE WATERPROOFED |
| AND DRAINED IN AN APPROVED MANNER. |
| |
| F] 416.2.1 SURFACES. THE INTERIOR SURFACES OF SPRAY |
| ROOMS SHALL BE SMOOTH AND SHALL BE SO CONSTRUCTED TO |
| PERMIT THE FREE PASSAGE OF EXHAUST AIR FROM ALL PARTS |
| OF THE INTERIOR AND TO FACILITATE WASHING AND CLEANING, |
| AND SHALL BE SO DESIGNED TO CONFINE RESIDUES WITHIN THE |
| ROOM. ALUMINUM SHALL NOT BE USED. |
| |
| |
| [F] 416.3 SPRAYING SPACES. SPRAYING SPACES SHALL BE |
| VENTILATED WITH AN EXHAUST SYSTEM TO PREVENT THE |
| ACCUMULATION OF FLAMMABLE MIST OR VAPORS IN ACCORDANCE |
| WITH THE FLORIDA BUILDING CODE, MECHANICAL . WHERE SUCH |
| SPACES ARE NOT SEPARATELY ENCLOSED, NONCOMBUSTIBLE |
| SPRAY CURTAINS SHALL BE PROVIDED TO RESTRICT THE SPREAD |
| OF FLAMMABLE VAPORS. |
| |
| |
| [F] 416.3.1 SURFACES. THE INTERIOR SURFACES OF SPRAYING |
| SPACES SHALL BE SMOOTH AND CONTINUOUS WITHOUT EDGES; |
| SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE OF |
| EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO |
| FACILITATE WASHING AND CLEANING; AND SHALL BE SO |
| DESIGNED TO CONFINE RESIDUES WITHIN THE SPRAYING SPACE. |
| ALUMINUM SHALL NOT BE USED. |
| |
| |
| [F] 416.4 FIRE PROTECTION. AN AUTOMATIC |
| FIRE-EXTINGUISHING SYSTEM SHALL BE PROVIDED IN ALL |
| SPRAY, DIP AND IMMERSING SPACES AND STORAGE ROOMS AND |
| SHALL BE INSTALLED IN ACCORDANCE WITH CHAPTER 9. |
| |
| |
| 2) [F] 415.3 FIRE SEPARATION DISTANCE. GROUP H |
| OCCUPANCIES SHALL BE LOCATED ON PROPERTY IN ACCORDANCE |
| WITH THE OTHER PROVISIONS OF THIS CHAPTER. IN GROUPS |
| H-2 AND H-3, NOT LESS THAN 25 PERCENT OF THE PERIMETER |
| WALL OF THE OCCUPANCY SHALL BE AN EXTERIOR WALL. |
| EXCEPTIONS: |
| 1. LIQUID USE, DISPENSING AND MIXING ROOMS HAVING A |
| FLOOR AREA OF NOT MORE THAN 500 SQUARE FEET (46.5 M2) |
| NEED NOT BE LOCATED ON THE OUTER PERIMETER OF THE |
| BUILDING WHERE THEY ARE IN ACCORDANCE WITH THE FLORIDA |
| FIRE PREVENTION CODE AND NFPA 30. |
| 2. LIQUID STORAGE ROOMS HAVING A FLOOR AREA OF NOT MORE |
| THAN 1,000 SQUARE FEET (93 M2) NEED NOT BE LOCATED ON |
| THE OUTER PERIMETER WHERE THEY ARE IN ACCORDANCE WITH |
| THE FLORIDA FIRE PREVENTION CODE AND NFPA 30. |
| 3. SPRAY PAINT BOOTHS THAT COMPLY WITH THE FLORIDA FIRE |
| PREVENTION CODE NEED NOT BE LOCATED ON THE OUTER |
| PERIMETER. |
| |
| |
| 3) PLEASE PROVIDE THE AMOUNT OF SPRAYABLE LIQUIDS |
| INCLUDING THINNERS AND SOLVENTS. PLEASE SEE FBC-B TABLE |
| 307.1(1) FOR THE AMOUNTS OF COMBUSTIBLE LIQUIDS PER |
| CONTROL AREAS. |
| |
| F] 307.4 HIGH-HAZARD GROUP H-2. BUILDINGS AND |
| STRUCTURES CONTAINING MATERIALS THAT POSE A |
| DEFLAGRATION HAZARD OR A HAZARD FROM ACCELERATED |
| BURNING SHALL BE CLASSIFIED AS GROUP H-2. SUCH |
| MATERIALS SHALL INCLUDE, BUT NOT BE LIMITED TO, THE |
| FOLLOWING: |
| |
| CLASS I, II OR IIIA FLAMMABLE OR COMBUSTIBLE LIQUIDS |
| WHICH ARE USED OR STORED IN NORMALLY OPEN CONTAINERS OR |
| SYSTEMS, OR IN CLOSED CONTAINERS OR SYSTEMS PRESSURIZED |
| AT MORE THAN 15 PSI (103.4 KPA) GAGE. |
| F] 307.5 HIGH-HAZARD GROUP H-3. BUILDINGS AND |
| STRUCTURES CONTAINING MATERIALS THAT READILY SUPPORT |
| COMBUSTION OR THAT POSE A PHYSICAL HAZARD SHALL BE |
| CLASSIFIED AS GROUP H-3. SUCH MATERIALS SHALL INCLUDE, |
| BUT NOT BE LIMITED TO, THE FOLLOWING: |
| |
| CLASS I, II OR IIIA FLAMMABLE OR COMBUSTIBLE LIQUIDS |
| THAT ARE USED OR STORED IN NORMALLY CLOSED CONTAINERS |
| OR SYSTEMS PRESSURIZED AT 15 POUNDS PER SQUARE INCH |
| GAUGE (103.4 KPA) OR LESS |
| |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| NOTICE. |
| |
| OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| - 5:00 PM. |
| |
| JIM WITMER C. B. O. |
| COMMERCIAL COMBINATION PLAN REVIEW |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| CUSTOMER SERVICE SURVEY AT: |
| WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| |