2010-05-03 10:58:38 | BUILDING PLAN REVIEW |
| PERMIT: 10020008/ REV: 10040595 |
| ADD: 2420 MEDINA WAY |
| CONT: AIR-REF CO., INC |
| TEL: (561)719-0845 / CHRIS |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) SUBMITTALS INDICATE ADDTIONAL SCOPE OF WORK THE |
| ADDITION OF A KITHEN HOOD AND UNVENTED GAS LOG |
| FIREPLACE APPLIANCE. THE REVISION SHEET INDICATES |
| INCREASE IN VALUE OF WORK AS ZERO |
| DOLLARS! PLEASE PROVIDE THE ADDITIONAL INCREASE TO |
| CONTRACT PRICE FOR THIS REVISION. |
| W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| APPLICABLE GOVERNING AUTHORITY. |
| |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 2) THE GAS PERMIT WILL ALSO NEED TO SHOW AN INCREASE IN |
| THEIR SCOPE OF WORK SINCE PERMIT # 10030670 DOES NOT |
| INDICATE ANY GAS PIPING BEING INSTALLED TO THIS NEW GAS |
| APPLIANCE. |
| |
| 3) THE SUBMITTAL FOR THE UNVENTED GAS LOG APPLIANCE |
| SPEC IS ONLY FOR THE IRE PLACE, WITHOUT THE |
| SPECIFICATION ON THE GAS LOGS WE CAN NOT PASS THIS |
| REVISION, IT MAY REQUIRE VENTILATION DEPENDING ON THE |
| SIZE OR BTU OF THE GAS LOGS. |
| 2007 FBC-M 903.3 UNVENTED GAS LOG HEATERS. AN UNVENTED |
| GAS LOG HEATER SHALL NOT BE INSTALLED IN A |
| FACTORY-BUILT FIREPLACE UNLESS THE FIREPLACE SYSTEM HAS |
| BEEN SPECIFICALLY TESTED, LISTED AND LABELED FOR SUCH |
| USE IN ACCORDANCE WITH UL 127. |
| 2007 FBC-G 602.1 GENERAL. DECORATIVE APPLIANCES FOR |
| INSTALLATION IN APPROVED SOLID FUEL-BURNING FIREPLACES |
| SHALL BE TESTED IN ACCORDANCE WITH ANSI Z21.60 AND |
| SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| MANUFACTURER'S INSTALLATION INSTRUCTIONS. MANUALLY |
| LIGHTED NATURAL GAS DECORATIVE APPLIANCES SHALL BE |
| TESTED IN ACCORDANCE WITH ANSI Z21.84. |
| |
| 4) 2007 FBC-M 903.2 HEARTH EXTENSIONS. HEARTH |
| EXTENSIONS OF APPROVED FACTORY-BUILT FIREPLACES AND |
| FIREPLACE STOVES SHALL BE INSTALLED IN ACCORDANCE WITH |
| THE LISTING OF THE FIREPLACE. THE HEARTH EXTENSION |
| SHALL BE READILY DISTINGUISHABLE FROM THE SURROUNDING |
| FLOOR AREA. |
| |
| 5) REVISION FOR THE NEW MECHANICAL KITCHEN HOOD, |
| SUBMITTAL FOR HOOD BUT NO INFORMATION IS PROVIDED FOR |
| HOW THE DUCT WILL BE VENTED, AND WHERE? ADDITIONAL |
| INFORMATION REQUIRED 106.1.2. |
| |
| 6) SECOND FLOOR AS BUILTS: A THOROUGH REVIEW CAN NOT BE |
| MADE AT THIS TIME, AS A RESULT OF THE ADDITIONAL |
| INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR |
| THAT WERE NOT PART OF THIS REVIEW. |
| 6A) MASTER BEDROOM IT APPEARS THERE IS A RIGHT ANGLE |
| TRANSITION FROM 11" DUCT TO 8" DUCT IS THERE A GRILLE |
| NOT IDENTIFIED? |
| |
| 6B) TRANSFER DUCTS IN BOTH THE MASTER BEDROOM AND |
| BEDROOM #1 ARE NOT IDENTIFIED? FBC-M 601.4. |
| |
| 6C) MASTER BEDROOM CLOSET THE SUPPLY DUCT SIZE IS NOT |
| IDENTIFIED? 106.1.2 ADDITIONAL INFORMATION REQUIED. |
| |
| 6D) GUEST BATH #1 SUPPLY DUCT SIZE IS NOT PROVIDED. |
| 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| |
| 6E) ROOM 28 SUPPLY DUCT SIZE IS NOT PROVIDED. 106.1.2 |
| ADDITIONAL INFORMATION REQUIRED. |
| |
| 6F) STUDY RETURN AIR DUCT SIZE IS NOT PROVIDED. THERE |
| ALSO APPEARS TO BE A RETURN AIR WITHIN THE WALL AGAIN |
| THE SIZE IS NOT PROVIDED. 106.1.2 |
| |
| 6G) 2ND FLOOR STAIR HALL INDICATES A 24"X24" RETURN IS |
| THIS RETURN DUCTED TO THE AIR HANDLIER OR IS THIS A |
| TRANSFER GRILLE, UNCLEAR AS TO LOCATION OF THE AIR |
| HANDLIER. FBC-M601.4. |
| |
| JIM WITMER C. B. O. |
| COMMERCIAL COMBINATION PLAN REVIEW |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| CUSTOMER SERVICE SURVEY AT: |
| WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |