2010-05-03 10:58:38BUILDING PLAN REVIEW
 PERMIT: 10020008/ REV: 10040595
 ADD: 2420 MEDINA WAY
 CONT: AIR-REF CO., INC
 TEL: (561)719-0845 / CHRIS
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SUBMITTALS INDICATE ADDTIONAL SCOPE OF WORK THE
 ADDITION OF A KITHEN HOOD AND UNVENTED GAS LOG
 FIREPLACE APPLIANCE. THE REVISION SHEET INDICATES
 INCREASE IN VALUE OF WORK AS ZERO
 DOLLARS! PLEASE PROVIDE THE ADDITIONAL INCREASE TO
 CONTRACT PRICE FOR THIS REVISION.
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THE GAS PERMIT WILL ALSO NEED TO SHOW AN INCREASE IN
 THEIR SCOPE OF WORK SINCE PERMIT # 10030670 DOES NOT
 INDICATE ANY GAS PIPING BEING INSTALLED TO THIS NEW GAS
 APPLIANCE.
  
 3) THE SUBMITTAL FOR THE UNVENTED GAS LOG APPLIANCE
 SPEC IS ONLY FOR THE IRE PLACE, WITHOUT THE
 SPECIFICATION ON THE GAS LOGS WE CAN NOT PASS THIS
 REVISION, IT MAY REQUIRE VENTILATION DEPENDING ON THE
 SIZE OR BTU OF THE GAS LOGS.
 2007 FBC-M 903.3 UNVENTED GAS LOG HEATERS. AN UNVENTED
 GAS LOG HEATER SHALL NOT BE INSTALLED IN A
 FACTORY-BUILT FIREPLACE UNLESS THE FIREPLACE SYSTEM HAS
 BEEN SPECIFICALLY TESTED, LISTED AND LABELED FOR SUCH
 USE IN ACCORDANCE WITH UL 127.
 2007 FBC-G 602.1 GENERAL. DECORATIVE APPLIANCES FOR
 INSTALLATION IN APPROVED SOLID FUEL-BURNING FIREPLACES
 SHALL BE TESTED IN ACCORDANCE WITH ANSI Z21.60 AND
 SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. MANUALLY
 LIGHTED NATURAL GAS DECORATIVE APPLIANCES SHALL BE
 TESTED IN ACCORDANCE WITH ANSI Z21.84.
  
 4) 2007 FBC-M 903.2 HEARTH EXTENSIONS. HEARTH
 EXTENSIONS OF APPROVED FACTORY-BUILT FIREPLACES AND
 FIREPLACE STOVES SHALL BE INSTALLED IN ACCORDANCE WITH
 THE LISTING OF THE FIREPLACE. THE HEARTH EXTENSION
 SHALL BE READILY DISTINGUISHABLE FROM THE SURROUNDING
 FLOOR AREA.
  
 5) REVISION FOR THE NEW MECHANICAL KITCHEN HOOD,
 SUBMITTAL FOR HOOD BUT NO INFORMATION IS PROVIDED FOR
 HOW THE DUCT WILL BE VENTED, AND WHERE? ADDITIONAL
 INFORMATION REQUIRED 106.1.2.
  
 6) SECOND FLOOR AS BUILTS: A THOROUGH REVIEW CAN NOT BE
 MADE AT THIS TIME, AS A RESULT OF THE ADDITIONAL
 INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR
 THAT WERE NOT PART OF THIS REVIEW.
 6A) MASTER BEDROOM IT APPEARS THERE IS A RIGHT ANGLE
 TRANSITION FROM 11" DUCT TO 8" DUCT IS THERE A GRILLE
 NOT IDENTIFIED?
  
 6B) TRANSFER DUCTS IN BOTH THE MASTER BEDROOM AND
 BEDROOM #1 ARE NOT IDENTIFIED? FBC-M 601.4.
  
 6C) MASTER BEDROOM CLOSET THE SUPPLY DUCT SIZE IS NOT
 IDENTIFIED? 106.1.2 ADDITIONAL INFORMATION REQUIED.
  
 6D) GUEST BATH #1 SUPPLY DUCT SIZE IS NOT PROVIDED.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 6E) ROOM 28 SUPPLY DUCT SIZE IS NOT PROVIDED. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 6F) STUDY RETURN AIR DUCT SIZE IS NOT PROVIDED. THERE
 ALSO APPEARS TO BE A RETURN AIR WITHIN THE WALL AGAIN
 THE SIZE IS NOT PROVIDED. 106.1.2
  
 6G) 2ND FLOOR STAIR HALL INDICATES A 24"X24" RETURN IS
 THIS RETURN DUCTED TO THE AIR HANDLIER OR IS THIS A
 TRANSFER GRILLE, UNCLEAR AS TO LOCATION OF THE AIR
 HANDLIER. FBC-M601.4.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved