Plan Review Notes For Permit 10040588 |
Permit Number |
10040588 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-04-22 16:40:38 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- FLAT ROOF: PROVIDE RAS 117 CALCULATIONS FOR NAIL | | ENHANCING AT PERIMETER AND CORNER AREAS TO MEET THE | | DESIGN PRESSURES OF SEC. R301 OF 2007 FLORIDA | | RESIDENTIAL CODE AND GENERAL LIMITATION #7 ON LAST PAGE | | OF NOA 05-0830.10 SUBMITTED. | | ***NOTE: THIS BUILDING IS LOCATED IN EXPOSURE "C". TAKE | | THIS INTO CONSIDERATION WHEN DOING THE RAS 117 | | CALCULATIONS. | | | | 2- CLEARLY IDENTIFY WHICH APPROVED FLAT ROOF ASSEMBLY | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH SEC | | R301 AND TO COORDINATE WITH ITEM #1 ABOVE. | | | | 3- ROOFING OVER EXISTING ROOF NEEDS PRE-INSPECTION. | | SEPARATE PERMIT WAS APPLIED FOR. WAITING FOR INSPECTOR | | FINDINGS TO ISSUE SHINGLES ROOF OVER PERMIT. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 | | |
|