2010-04-22 16:40:38RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- FLAT ROOF: PROVIDE RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS TO MEET THE
 DESIGN PRESSURES OF SEC. R301 OF 2007 FLORIDA
 RESIDENTIAL CODE AND GENERAL LIMITATION #7 ON LAST PAGE
 OF NOA 05-0830.10 SUBMITTED.
 ***NOTE: THIS BUILDING IS LOCATED IN EXPOSURE "C". TAKE
 THIS INTO CONSIDERATION WHEN DOING THE RAS 117
 CALCULATIONS.
  
 2- CLEARLY IDENTIFY WHICH APPROVED FLAT ROOF ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH SEC
 R301 AND TO COORDINATE WITH ITEM #1 ABOVE.
  
 3- ROOFING OVER EXISTING ROOF NEEDS PRE-INSPECTION.
 SEPARATE PERMIT WAS APPLIED FOR. WAITING FOR INSPECTOR
 FINDINGS TO ISSUE SHINGLES ROOF OVER PERMIT.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  