2010-05-10 20:41:49*****DENIED*****
  
  
 1. THE SPECIFICATIONS PACKAGE INCLUDES INFORMATION FOR
 SINGLE-ENDED REFLECTED TYPE BEAM SMOKE DETECTORS
 INSTEAD OF HEAT DETECTORS AS LISTED IN THE FIRE ALARM
 PLAN.
  
 2. ON SHEET FA-2, THE FLOOR PLAN / FIRE ALARM SYSTEM
 LAYOUT IS TOO SMALL. ENLARGE THE DRAWING TO CLEARLY AND
 DISTINCTLY SHOW/LIST THE DEVICES AND THEIR
 CORRESPONDING ADDRESSES.
  
 3. THE PLAN INDICATES THAT SMOKE DETECTORS ARE
 INSTALLED IN THE SLEEPING ROOMS. PLEASE FAMILIARIZE
 YOURSELF AND BE ADVISED OF THE SMOKE ALARM REQUIREMENTS
 AS PER 32.2.3.4.3 OF 2006 NFPA 101 - LIFE SAFETY CODE -
 FLORIDA 2007 EDITION. ATTENTION: IN LIEU OF SMOKE
 ALARMS, FIRE ALARM SYSTEM SMOKE DETECTORS IN ACCORDANCE
 WITH NFPA 72 SHALL BE PERMITTED IF SO ARRANGED TO
 FUNCTION IN THE SAME MANNER AS SMOKE ALARMS.
  
 4. IN NEW CONSTRUCTION AND/OR CONVERSIONS, WHERE TWO OR
 MORE ALARMS ARE INSTALLED WITHIN A DWELLING UNIT, SUITE
 OF ROOMS, OR SIMILAR AREA, SHALL BE ARRANGED SO THAT
 THE OPERATION OF ANY SMOKE ALARM SHALL CAUSE ALL ALARMS
 WITHIN THESE LOCATIONS TO SOUND. SMOKE ALARMS SHALL
 RECEIVE THEIR OPERATING POWER FROM THE BUILDING
 ELECTRICAL SYSTEM.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW