Plan Review Notes For Permit 10040490 |
Permit Number |
10040490 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-05-10 20:41:49 | *****DENIED***** | | | | | | 1. THE SPECIFICATIONS PACKAGE INCLUDES INFORMATION FOR | | SINGLE-ENDED REFLECTED TYPE BEAM SMOKE DETECTORS | | INSTEAD OF HEAT DETECTORS AS LISTED IN THE FIRE ALARM | | PLAN. | | | | 2. ON SHEET FA-2, THE FLOOR PLAN / FIRE ALARM SYSTEM | | LAYOUT IS TOO SMALL. ENLARGE THE DRAWING TO CLEARLY AND | | DISTINCTLY SHOW/LIST THE DEVICES AND THEIR | | CORRESPONDING ADDRESSES. | | | | 3. THE PLAN INDICATES THAT SMOKE DETECTORS ARE | | INSTALLED IN THE SLEEPING ROOMS. PLEASE FAMILIARIZE | | YOURSELF AND BE ADVISED OF THE SMOKE ALARM REQUIREMENTS | | AS PER 32.2.3.4.3 OF 2006 NFPA 101 - LIFE SAFETY CODE - | | FLORIDA 2007 EDITION. ATTENTION: IN LIEU OF SMOKE | | ALARMS, FIRE ALARM SYSTEM SMOKE DETECTORS IN ACCORDANCE | | WITH NFPA 72 SHALL BE PERMITTED IF SO ARRANGED TO | | FUNCTION IN THE SAME MANNER AS SMOKE ALARMS. | | | | 4. IN NEW CONSTRUCTION AND/OR CONVERSIONS, WHERE TWO OR | | MORE ALARMS ARE INSTALLED WITHIN A DWELLING UNIT, SUITE | | OF ROOMS, OR SIMILAR AREA, SHALL BE ARRANGED SO THAT | | THE OPERATION OF ANY SMOKE ALARM SHALL CAUSE ALL ALARMS | | WITHIN THESE LOCATIONS TO SOUND. SMOKE ALARMS SHALL | | RECEIVE THEIR OPERATING POWER FROM THE BUILDING | | ELECTRICAL SYSTEM. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|