2010-09-21 14:27:46 | 355 EDMORE ROAD |
| PERMIT NUMBER 10040488 |
| FIRE ALARM SYSTEM INSTALLATION |
| |
| |
| 1. AFTER SEVERAL MEETINGS AND TELEPHONE CALLS, THE |
| PLANS CONSIST OF SHEET FA-1 AND FA-2. THE FIRE ALARM |
| INSTALLATION CONSISTS OF THE INSTALLATION OF MANUAL |
| PULL STATIONS, CEILING HORN STROBES, AND STROBE LIGHTS. |
| |
| 2. PER SECTION 32.2.3.4.1 "A MANUAL FIRE ALARM SYSTEM |
| SHALL BE PROVIDED IN ACCORDANCE WITH 9.6." (FLORIDA |
| FIRE PREVENTION CODE, LIFE SAFETY CODE, 101, 2006 |
| EDITION) |
| |
| 3. PER SECTION 32.2.3.4.2 "OCCUPANT NOTIFICATION SHALL |
| BE PROVIDED AUTOMATICALLY, WITHOUT DELAY, IN ACCORDANCE |
| WITH 9.6.3" (FLORIDA FIRE PREVENTION CODE, LIFE SAFETY |
| CODE, 101, 2006 EDITION) |
| |
| 4. NOT PART OF THIS PLAN: "APPROVED SMOKE ALARMS SHALL |
| BE PROVIDED IN ACCORDANCE WITH 9.6.2.9" (FLORIDA FIRE |
| PREVENTION CODE, LIFE SAFETY CODE, 101, 2006 EDITION, |
| SECTION 32.2.3.4.3.1) |
| |
| 5. "SMOKE ALARM SHALL BE INSTALLED ON ALL LEVELS, |
| INCLUDING BASEMENTS, BUT EXCLUDING CRAWL SPACES AND |
| UNFINISHED ATTICS" (FLORIDA FIRE PREVENTION CODE, LIFE |
| SAFETY CODE, 101, 2006 EDITION, SECTION 32.2.3.4.3.2) |
| |
| 6. "ADDITIONAL SMOKE ALARMS SHALL BE INSTALLED IN ALL |
| LIVING AREAS, AS DEFINED IN 3.3.17.5" (FLORIDA FIRE |
| PREVENTION CODE, LIFE SAFETY CODE, 101, 2006 EDITION, |
| SECTION 32.2.3.4.3.3) |
| |
| 7. "EACH SLEEPING ROOM SHALL BE PROVIDED WITH AN |
| APPROVED SMOKE ALARM IN ACCORDANCE WITH 9.6.2.9" |
| (FLORIDA FIRE PREVENTION CODE, 101, 2006 EDITION, |
| SECTION 32.2.3.4.3.4) |
| |
| 8) THE FIRE ALARM SYSTEM INSTALLATION TO BE TESTED WITH |
| REPRESENTATIVES OF THIS OFFICE. |
| |
| 9) FIRE ALARM INSTALLATION SUBJECT TO FIELD INSPECTION |
| AND APPROVAL. |
| |
| |
| APPROVED |
| |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| BUREAU OF FIRE PREVENTION |