Plan Review Notes
Plan Review Notes For Permit 10040488
Permit Number 10040488
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2010-09-21 14:27:46355 EDMORE ROAD
 PERMIT NUMBER 10040488
 FIRE ALARM SYSTEM INSTALLATION
  
  
 1. AFTER SEVERAL MEETINGS AND TELEPHONE CALLS, THE
 PLANS CONSIST OF SHEET FA-1 AND FA-2. THE FIRE ALARM
 INSTALLATION CONSISTS OF THE INSTALLATION OF MANUAL
 PULL STATIONS, CEILING HORN STROBES, AND STROBE LIGHTS.
  
 2. PER SECTION 32.2.3.4.1 "A MANUAL FIRE ALARM SYSTEM
 SHALL BE PROVIDED IN ACCORDANCE WITH 9.6." (FLORIDA
 FIRE PREVENTION CODE, LIFE SAFETY CODE, 101, 2006
 EDITION)
  
 3. PER SECTION 32.2.3.4.2 "OCCUPANT NOTIFICATION SHALL
 BE PROVIDED AUTOMATICALLY, WITHOUT DELAY, IN ACCORDANCE
 WITH 9.6.3" (FLORIDA FIRE PREVENTION CODE, LIFE SAFETY
 CODE, 101, 2006 EDITION)
  
 4. NOT PART OF THIS PLAN: "APPROVED SMOKE ALARMS SHALL
 BE PROVIDED IN ACCORDANCE WITH 9.6.2.9" (FLORIDA FIRE
 PREVENTION CODE, LIFE SAFETY CODE, 101, 2006 EDITION,
 SECTION 32.2.3.4.3.1)
  
 5. "SMOKE ALARM SHALL BE INSTALLED ON ALL LEVELS,
 INCLUDING BASEMENTS, BUT EXCLUDING CRAWL SPACES AND
 UNFINISHED ATTICS" (FLORIDA FIRE PREVENTION CODE, LIFE
 SAFETY CODE, 101, 2006 EDITION, SECTION 32.2.3.4.3.2)
  
 6. "ADDITIONAL SMOKE ALARMS SHALL BE INSTALLED IN ALL
 LIVING AREAS, AS DEFINED IN 3.3.17.5" (FLORIDA FIRE
 PREVENTION CODE, LIFE SAFETY CODE, 101, 2006 EDITION,
 SECTION 32.2.3.4.3.3)
  
 7. "EACH SLEEPING ROOM SHALL BE PROVIDED WITH AN
 APPROVED SMOKE ALARM IN ACCORDANCE WITH 9.6.2.9"
 (FLORIDA FIRE PREVENTION CODE, 101, 2006 EDITION,
 SECTION 32.2.3.4.3.4)
  
 8) THE FIRE ALARM SYSTEM INSTALLATION TO BE TESTED WITH
 REPRESENTATIVES OF THIS OFFICE.
  
 9) FIRE ALARM INSTALLATION SUBJECT TO FIELD INSPECTION
 AND APPROVAL.
  
  
 APPROVED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION