Plan Review Notes For Permit 10040468 |
Permit Number |
10040468 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-04-28 11:26:02 | PLAN PASS PROVISO | | 1) PLEASE REFER TO SECTION 301.21 FBC (M) 2007 WIND | | RESISTANCE. MECHANICAL EQUIPMENT , APPLIANCES AND | | SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND | | INSTALLED TO RESIST THE WIND PRESSURES ON THE EQUIPMENT | | AND SUPPORTS | | 2) PLEASE REFER TO SECTION 606.2.1 2007 FBC (M) SUPPLY | | SYSTEMS SMOKE DETECTORS SHALL BE INSTALLED IN THE | | SUPPLY AIR SYSTEM WITH A DESIGN CAPACITY GREATER THAN | | 2000 CFM IN THE SUPPLY DUCT ( FRESH AIR) | | 3) PLEASE REFER TO SECTION 506.3.12.3 2007 FBC (M) | | TREMINATION LOCATION . | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|