Plan Review Notes
Plan Review Notes For Permit 10040465
Permit Number 10040465
Review Stop B
Sequence Number 1
Notes
Date Text
2010-04-19 17:07:48RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- A) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS
 FOR NAIL ENHANCING AS REQUIRED BY GENERAL LIMITATION #7
 ON NOA 06-0410.06 SUBMITTED TO MEET THE DESIGN
 PRESSURES OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL
 CODE.
  
 B) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS
 TO CONSIDER THAT ACCORDING TO SEC. R301.2.1.4.3 OF 2009
 FLORIDA RESIDENTIAL CODE THIS BUILDING IS LOCATED ON
 EXPOSURE "C".
  
 2- POLYGLASS MODIFIED BITUMEN NOA 06-0410.06 IS CLOSED
 BY MIAMI-DADE. GO TO MIAMI-DADE PRODUCT APPROVAL
 WEBSITE AND DOWNLOAD CURRENT NOA.
  
 3- A) SPECIFY HOW IS ROOF TILE GOING TO BE INSTALLED TO
 VERIFY DESIGN PRESSURES OF SEC. R301.
  
 B) IF USING POLYFOAM, THEN PROVIDE PRODUCT APPROVAL AS
 REQUIRED BY DCA RULE 9B-72.
  
 4- SPECIFY SQUARE FOOTAGE FOR PITCHED ROOF AND SQUARE
 FOOTAGE FOR FLAT ROOF TO VERIFY PERMIT VALUATION AS
 REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC.
  
 5- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712