Plan Review Notes For Permit 10040465 |
Permit Number |
10040465 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-04-19 17:07:48 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- A) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS | | FOR NAIL ENHANCING AS REQUIRED BY GENERAL LIMITATION #7 | | ON NOA 06-0410.06 SUBMITTED TO MEET THE DESIGN | | PRESSURES OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL | | CODE. | | | | B) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS | | TO CONSIDER THAT ACCORDING TO SEC. R301.2.1.4.3 OF 2009 | | FLORIDA RESIDENTIAL CODE THIS BUILDING IS LOCATED ON | | EXPOSURE "C". | | | | 2- POLYGLASS MODIFIED BITUMEN NOA 06-0410.06 IS CLOSED | | BY MIAMI-DADE. GO TO MIAMI-DADE PRODUCT APPROVAL | | WEBSITE AND DOWNLOAD CURRENT NOA. | | | | 3- A) SPECIFY HOW IS ROOF TILE GOING TO BE INSTALLED TO | | VERIFY DESIGN PRESSURES OF SEC. R301. | | | | B) IF USING POLYFOAM, THEN PROVIDE PRODUCT APPROVAL AS | | REQUIRED BY DCA RULE 9B-72. | | | | 4- SPECIFY SQUARE FOOTAGE FOR PITCHED ROOF AND SQUARE | | FOOTAGE FOR FLAT ROOF TO VERIFY PERMIT VALUATION AS | | REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC. | | | | 5- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | FLORIDA STATUTE. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|