Plan Review Notes
Plan Review Notes For Permit 10040384
Permit Number 10040384
Review Stop B
Sequence Number 2
Notes
Date Text
2010-05-26 12:59:28RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW SECOND
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ROOF CALCULATIONS SUBMITTED:
  
 A) ENGINEER TO PROVIDE ACTUAL RAS 117 CALCULATIONS.
 FASTENING OPTION #1 ON PAGE 5 OF NOA 08-0924.14
 SUBMITTED IS GOOD ONLY FOR -60PSF. IT CAN'T BE USED FOR
 ALL ROOF ZONES AS SPECIFIED BY THE ENGINEER. PERIMETER
 AND CORNER AREAS REQUIRE HIGHER DESIGN PRESSURES.
  
 B) PROVIDE ACTUAL CALCULATIONS FOR COMPONENTS AND
 CLADDING. INFORMATION SUBMITTED IS INCORRECT.
 CALCULATED DESIGN PRESSURES ARE NOT FOR EXPOSURE "C".
 REVISE AS REQUIRED.
  
 C) CURRENT CODE IS THE 2007 FLORIDA RESIDENTIAL CODE
 WITH 2009 REVISIONS. ENGINEER TO REFER TO ASCE 7-05 NOT
 ASCE 7-02.
  
 D) ENGINEER TO PROVIDE ALL HIS INFORMATION AS REQUIRED
 BY CHAPTER 471 FLORIDA STATUTE AND FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002(2). MISSING THE
 ENGINEER'S ADDRESS.
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712