2010-05-26 12:59:28 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW SECOND | | CHECKLIST. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- ROOF CALCULATIONS SUBMITTED: | | | | A) ENGINEER TO PROVIDE ACTUAL RAS 117 CALCULATIONS. | | FASTENING OPTION #1 ON PAGE 5 OF NOA 08-0924.14 | | SUBMITTED IS GOOD ONLY FOR -60PSF. IT CAN'T BE USED FOR | | ALL ROOF ZONES AS SPECIFIED BY THE ENGINEER. PERIMETER | | AND CORNER AREAS REQUIRE HIGHER DESIGN PRESSURES. | | | | B) PROVIDE ACTUAL CALCULATIONS FOR COMPONENTS AND | | CLADDING. INFORMATION SUBMITTED IS INCORRECT. | | CALCULATED DESIGN PRESSURES ARE NOT FOR EXPOSURE "C". | | REVISE AS REQUIRED. | | | | C) CURRENT CODE IS THE 2007 FLORIDA RESIDENTIAL CODE | | WITH 2009 REVISIONS. ENGINEER TO REFER TO ASCE 7-05 NOT | | ASCE 7-02. | | | | D) ENGINEER TO PROVIDE ALL HIS INFORMATION AS REQUIRED | | BY CHAPTER 471 FLORIDA STATUTE AND FLORIDA | | ADMINISTRATIVE CODE SEC. 61G15-23.002(2). MISSING THE | | ENGINEER'S ADDRESS. | | | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|