Plan Review Notes For Permit 10040384 |
Permit Number |
10040384 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-04-19 10:31:30 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS ( 2 | | COPIES) AS REQUIRED BY GENERAL LIMITATION #7 ON LAST | | PAGE OF MULE-HIDE PRODUCTS CO. INC NOA 08-0924.14 | | SUBMITTED. | | | | 2- CLARIFY WHICH APPROVED ASSEMBLY IS GOING TO BE | | INSTALLED. IS IT AN INSULATED SYSTEM AS SHOWN ON PAGE 5 | | SUBMITTED. OR IS IT A NON-INSULATED SYSTEM AS SHOWN ON | | PAGE 34 SUBMITTED. | | ***NOTE: NON-INSULATED SYSTEM ON PAGE 34 CAN'T NOT BE | | USED BECAUSE IT DOESN'T MEET THE DESIGN PRESSURES | | REQUIRED BY SEC. 301 OF 2007 FLORIDA RESIDENTIAL CODE. | | AND, GENERAL LIMITATION #9 DOESN'T ALLOW NAIL | | ENHANCING. SEE LAST PAGE OF NOA SUBMITTED. | | | | 3- DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS | | TO TAKE INTO CONSIDERATION THAT THIS BUILDING IS | | LOCATED ON EXPOSURE "C" AS REQUIRED BY SEC. | | R301.2.1.4.3 OF 2009 REVISIONS TO THE 2007 FLORIDA | | RESIDENTIAL CODE. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|