Plan Review Notes
Plan Review Notes For Permit 10040384
Permit Number 10040384
Review Stop B
Sequence Number 1
Notes
Date Text
2010-04-19 10:31:30RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS ( 2
 COPIES) AS REQUIRED BY GENERAL LIMITATION #7 ON LAST
 PAGE OF MULE-HIDE PRODUCTS CO. INC NOA 08-0924.14
 SUBMITTED.
  
 2- CLARIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED. IS IT AN INSULATED SYSTEM AS SHOWN ON PAGE 5
 SUBMITTED. OR IS IT A NON-INSULATED SYSTEM AS SHOWN ON
 PAGE 34 SUBMITTED.
 ***NOTE: NON-INSULATED SYSTEM ON PAGE 34 CAN'T NOT BE
 USED BECAUSE IT DOESN'T MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. 301 OF 2007 FLORIDA RESIDENTIAL CODE.
 AND, GENERAL LIMITATION #9 DOESN'T ALLOW NAIL
 ENHANCING. SEE LAST PAGE OF NOA SUBMITTED.
  
 3- DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS
 TO TAKE INTO CONSIDERATION THAT THIS BUILDING IS
 LOCATED ON EXPOSURE "C" AS REQUIRED BY SEC.
 R301.2.1.4.3 OF 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712