Plan Review Notes For Permit 10040347 |
Permit Number |
10040347 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-04-22 10:33:06 | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2 | | RESIDENTIAL FLORIDA BUILDING CODE. INDICATE LOCATIONS | | ON PLAN. | | | | 2} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH | | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. LOCATE ON | | THE PLANS. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | | | |
|