Plan Review Notes
Plan Review Notes For Permit 10040327
Permit Number 10040327
Review Stop B
Sequence Number 2
Notes
Date Text
2010-07-08 09:29:16****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 2. AS THIS IS AN AREA OF QUESTIONABLE SOILS (NOTE THAT
 THIS PARCEL IS FIVE LOTS AWAY FROM A FLOOD ZONE),
 PLEASE PROVIDE A SOILS INVESTIGATION REPORT FBC R301 IN
 ORDER TO CONFIRM THAT THE ENGINEER'S FOOTING DESIGN IS
 ADEQUATE TO SUPPORT THE EXISTING AND PROPOSED
 CONSTRUCTION. ALTERNATIVELY, ENGINEER CAN CONTACT ME IF
 HE FEELS THAT HE HAS ENOUGH INFORMATION TO DETERMINE
 THIS WITHOUT A SOILS INVESTIGATION REPORT.
  
 DESIGN IS BASED ON 2500PSF. PLEASE DEMONSTRATE THAT THE
 SOIL HAS A BEARING CAPACITY OF 2500PSF MINIMUM. AS
 DISCUSSED WITH CONTRACTOR, THIS MAY BE IN THE FORM OF
 JUSTIFICATION FROM ENGINEER OR A SOILS INVESTIGATION
 REPORT.
  
  
  
  